90
Main Setup [200]
Section 11-2
In this menu you set the general rotation for the motor.
Communication information
11-2-2 Remote Signal Level/Edge [21A]
In this menu you select the way to control the inputs for RunR, RunL, Stop and
Reset that are operated via the digital inputs on the terminal strip. The inputs
are default set for level-control, and will be active as long as the input is made
and kept high. When edge-control is selected, the input will be activated by
the low to high transition of the input.
Communication information
!Caution
Level controlled inputs DO NOT comply with the Machine Directive if the
inputs are directly used to start and stop the machine.
Note
Edge controlled inputs can comply with the Machine Directive (see the
Chapter SECTION 8 page 65) if the inputs are directly used to start and stop
the machine.
Default:
R + L
R
1
Speed direction is limited to right rotation. The input and
key RunL are disabled.
L
2
Speed direction is limited to left rotation. The input and key
RunR are disabled.
R+L
3
Both speed directions allowed.
Modbus Instance no/
DeviceNet no:
43019
Profibus slot/index
168/178
EtherCAT index (hex)
4bcb
Fieldbus format
UInt
Modbus format
UInt
219 Rotation
Stp
R+L
A
Default:
Level
Level
0
The inputs are activated or deactivated by a continuous
high or low signal. Is commonly used if, for example, a PLC
is used to operate the VSD.
Edge
1
The inputs are activated by a transition; for Run and Reset
from “low” to “high”, for Stop from “high” to “low”.
Modbus Instance no/
DeviceNet no:
43020
Profibus slot/index
168/179
EtherCAT index (hex)
4bcc
Fieldbus format
UInt
Modbus format
UInt
Level
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...