91
Main Setup [200]
Section 11-2
11-2-3 Mains supply voltage [21B]
!Warning
This menu must be set according to the VSD product lable and the supply
voltage used. Wrong setting might damage the VSD or brake resistor.
In this menu the nominal mains supply voltage connected to the VSD can be
selected. The setting will be valid for all parameter sets. The default setting,
Not defined, is never selectable and is only visible until a new value is
selected.
Once the supply voltage is set, this selection will not be affected by the Load
Default command [243].
Brake chopper activation level is adjusted using the setting of [21B].
Note
The setting is affected by the Load from CP command [245] and if loading
parameter file via EmoSoftCom.
Communication information
11-2-4 Motor Data [220]
In this menu you enter the motor data to adapt the VSD to the connected
motor. This will increase the control accuracy as well as different read-outs
and analogue output signals.
Motor M1 is selected as default and motor data entered will be valid for motor
M1. If you have more than one motor you need to select the correct motor in
menu [212] before entering motor data.
Note
The parameters for motor data cannot be changed during run mode.
Note
The default settings are for a standard 4-pole motor according to the nominal
power of the VSD.
Note
Parameter set cannot be changed during run if the sets is set for different
motors.
Note
Motor Data in the different sets M1 to M4 can be revert to default setting in
menu [243], Default>Set.
Default:
Not defined
Not Defined
0
Inverter default value used. Only valid if this parameter is
never set.
220-240 V
1
Only valid for SX-F-4 (400V)
380-415 V
3
Only valid for SX-F-4 (400V)
440-480 V
4
Only valid for SX-F-4 (400V)
500-525 V
5
Only valid for SX-F-6 (690V)
550-600 V
6
Only valid for SX-F-6 (690V)
660-690 V
7
Only valid for SX-F-6 (690V)
Modbus Instance no/
DeviceNet no:
43381
Profibus slot/index
170/30
EtherCAT index (hex)
4d35
Fieldbus format
UInt
Modbus format
UInt
Not defined
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...