150
Process and Application Parameters [300]
Section 11-3
Flux Optimization automatically decreases the V/Hz ratio, depending on the
actual load of the motor when the process is in a steady situation. Fig. 79
shows the area within which the Flux Optimization is active.
Note
The maximum possible setting for parameter [355] is limited by Inom/Imot
*120% but not higher than 400%.
Communication information
11-3-7 Preset References [
]
Motor Potentiometer [361]
Sets the properties of the motor potentiometer function. See the parameter
DigIn1 [521] for the selection of the motor potentiometer function.
Communication information
Default:
Off
Off
0
Off. No power limit
1 - 400
1 -
400
1 - 400% of motor nominal power
355 Max Power
Stp
Off
A
Modbus Instance no/
DeviceNet no:
43145
Profibus slot/index
169/49
EtherCAT index (hex)
4c49
Fieldbus format
Long, 1=1%
Modbus format
EInt
Default:
Non Volatile
Volatile
0
After a stop, trip or power down, the VSD will start always
from zero speed (or minimum speed, if selected).
Non volatile
1
Non Volatile. After a stop, trip or power down of the VSD,
the reference value at the moment of the stop will be mem-
orized. After a new start command the output speed will
resume to this saved value.
Modbus Instance no/
DeviceNet no:
43131
Profibus slot/index
169/35
EtherCAT index (hex)
4c3b
Fieldbus format
UInt
Modbus format
UInt
Non Volatie
A
Summary of Contents for SX-F
Page 2: ......
Page 14: ...6 Table of contents...
Page 20: ...12 Glossary Section 1 6...
Page 32: ...24 Cabinet mounting Section 2 3...
Page 58: ...50 Connecting options Section 5 6...
Page 72: ...64 Load Monitor and Process Protection 400 Section 7 5...
Page 74: ...66 EMC standards Section 8 1...
Page 266: ...258 System Data 900 Section 11 9...
Page 274: ...266 Maintenance Section 12 3...
Page 284: ...276 Liquid cooling Section 13 12...