6-16
•
The fault retry function automatically resets and restarts the Inverter in the case the Inverter has an
overvoltage fault, overcurrent fault, or ground fault.
•
In the case of any other fault, the protective function operates instantly and the fault retry function does
not operate.
•
This function is to be used only if the user does not want to interrupt the mechanical system, even if this
function may damage the Inverter.
•
Set n40 for multi-function output to the following value so that external overtorque detection output will
be turned on.
Set value: 14 for fault retries
n48
Fault Retry
Changes during
operation
No
Setting
range
0 to 10
Unit of
setting
1
Default setting
0
Set Values
•
Set the number of fault retries required.
•
The count of fault retries will be cleared in any of the following cases.
The Inverter is normal for 10 minutes continuously after the latest fault retry was made.
Power supply to the Inverter is interrupted.
A fault reset is input.
6-7-5 Frequency Jump Function (n49 to n51)
•
The frequency jump function prevents the Inverter from generating frequencies that make the me-
chanical system resonate.
•
The frequency jump function can be used effectively to set two dead bands of a frequency reference.
n49
Jump Frequency 1
Changes during
operation
No
Setting
range
0.0 to 400 (Hz)
Unit of
setting
0.1 Hz
(see note)
Default setting
0.0
n50
Jump Frequency 2
Changes during
operation
No
Setting
range
0.0 to 400 (Hz)
Setting
range
0.1 Hz
(see note)
Unit of setting
0.0
n51
Jump Width
Changes during
operation
No
Setting
range
0.0 to 25.5 (Hz)
Unit of
setting
0.1 Hz
Default setting
0.0
Note
Values will be set in 0.1-Hz increments if the frequency is less than 100 Hz and 1-Hz increments if
the frequency is 100 Hz or greater.
Advanced Operation
Chapter 6
Summary of Contents for SYSDRIVE 3G3JV-A4002
Page 1: ...USER S MANUAL SYSDRIVE 3G3JV Compact Simplified Inverters Cat No I528 E1 04...
Page 3: ...USER S MANUAL Compact Simplified Inverter SYSDRIVE 3G3JVSERIES...
Page 16: ......
Page 20: ...Chapter 1 Overview 1 1 Function 1 2 Nomenclature 1...
Page 26: ...Chapter 2 Design 2 1 Installation 2 2 Wiring 2...
Page 57: ...Chapter 3 Preparing for Operation and Monitoring 3 1 Nomenclature 3 2 Outline of Operation 3...
Page 65: ...Chapter 4 Test Run 4 1 Procedure for Test Run 4 2 Operation Example 4...
Page 216: ...Chapter 10 List of Parameters 10...
Page 229: ...Chapter 11 Using the Inverter for a Motor 11...