6-18
H
Frequency Detection
•
The parameter n40 for multi-function output must be set for frequency detection output.
Set value: 2 for frequency detection
Frequency Detection Operation
Output
frequency
Detection width
±
2 Hz
Reset width
±
4 Hz
Frequency reference
Time
Frequency
detection
Time
H
Frequency Detection Levels 1 and 2
•
The parameter n40 for multi-function output must be set for frequency detection output.
Set value: 4 for frequency detection level 1 (Output frequency
y
n58)
Set value: 5 for frequency detection level 2 (Output frequency
x
n58)
•
Set the frequency detection level in n58.
n58
Frequency Detection Level
Changes during
operation
No
Setting
range
0.0 to 400 (Hz)
Unit of
setting
0.1 Hz
(see note)
Default setting
0.0
Advanced Operation
Chapter 6