2-9
Function/Constant List
First Functions (Constant Nos. 0 to 19)
Function
No.
Name
Description
Initial
setting
User
set
values
See
page
Password
setting
0
Password
0: Password (No. 00) setting/reading and
first function (constant Nos. 1 to 19)
reading possible
1
43
Constant
write-in
prohibit
1: First function (constant Nos. 0 to 19) set-
ting/reading possible
2: First and second function (constant Nos.
0 to 29) setting/reading possible
Constant
group se-
lection
3: First, second and third function (constant
Nos. 0 to 59) setting/reading possible
Fault con-
tents clear
6: Fault record clear
Constant
initializa-
tion
8: Initialize (multifunction terminal: initial
value setting)
9: Initialize (3-wire sequence)
Operation
method
selection
1
Run signal
selection 1
1st digit = 0: Main frequency reference-ex-
ternal terminals 11 and 13 in-
puts
1: Main frequency reference-op-
erator Fxxxx
2nd digit = 0: Run by external terminal run
command
1: Run by operator run com-
mand
0000
44
Stopping
method
selection
3rd digit = 0: Deceleration to a stop
1: Coasting to a stop
Output
voltage li-
mitter
Output volt-
age limitter
4th digit = 0: With output voltage limitter
1: Without output voltage limitter
56
V/f char-
acteristic
setting
2
Maximum
frequency
Setting unit: 0.1 Hz, setting range: 50.0 to
400.0 Hz
60.0 Hz
44
3
Maximum
voltage
Setting unit: 0.1 V, setting range: 0.1 to
255.0 V
200.0 V
44
4
Maximum
voltage fre-
quency
(base fre-
quency)
Setting unit: 0.1 Hz, setting range: 0.1 to
400.0 Hz
60.0 Hz
44
5
Intermediate
output fre-
quency
Setting unit: 0.1 Hz, setting range: 0.1 to
400.0 Hz
1.5 Hz
44
6
Intermediate
output fre-
quency volt-
age
Setting unit: 0.1 V, setting range: 0.1 to
255.0 V
12.0 V
44
"
Section 2-9
Summary of Contents for SYSDRIVE 3G3SV
Page 1: ...6 6 5 9 69 19 57 5 69 BB 69 BB 2SHUDWLRQ 0DQXDO...
Page 3: ...0 1 2 3...