Third Functions (Constant Nos. 30 to 49)
Function
No.
Name
Description
Initial
setting
User
set
values
See
Page
Stall Prevention
30
Level of stall
preventive
operation
during ac-
celeration
Setting unit: 1%, setting range 30% to
200%
Note: Stall prevention is not performed
during acceleration when 200% is set.
170%
48
31
Level of stall
preventive
operation
during run-
ning
Setting unit: 1%, setting range 30% to
200%
Note: stall prevention is not performed
during run when 200% is set.
160%
Multi-
func-
tion
selec-
tion
Contact
input
signal
32
Multifunction
input selec-
tion 1 (termi-
nal 7 func-
tion selec-
tion)
0: FWD/REV run command (3-WIRE se-
quence selection)
1: JOG command
2: Accel/decel time change
3: Multi-step speed reference 3
4: External baseblock (NO contact input)
5: External baseblock (NC contact input)
6: Speed search from max. frequency
7: Speed search from set frequency
1
49
33
Multifunction
input selec-
tion 2 (termi-
nal 8 func-
tion selec-
tion)
1: JOG command
2: Accel/decel time change
3: Multi-step speed reference 3
4: External baseblock (NO contact input)
5: External baseblock (NC contact input)
6: Speed search from max. frequency
7: Speed search from set frequency
2
Photo-
coupler
output
signal
34
Multifunction
input selec-
tion 1 (termi-
nal 14 func-
tion selec-
tion)
0: Running
1: Frequency coincidence
2: Zero speed
3: Frequency detection (output frequency
≥
frequency detection level)
4: Overtorque detection
0
50
35
Multifunction
input selec-
tion 2 (termi-
nal 15 func-
tion selec-
tion)
0: Running
1: Frequency coincidence
2: Zero speed
3: Frequency detection (output frequency
≥
frequency detection level)
4: Overtorque detection
1
Desired speed
detection
36
Frequency
detection
level
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0 Hz
0.0 Hz
51
"
Section 2-9
Summary of Contents for SYSDRIVE 3G3SV
Page 1: ...6 6 5 9 69 19 57 5 69 BB 69 BB 2SHUDWLRQ 0DQXDO...
Page 3: ...0 1 2 3...
Page 5: ...2 4 4 3 4 5 5 6 7 8 8...