(&
Terminal function at 3-WIRE sequence selection
3G3SV
1
2
7
9
Run command
(run at “closed”)
Stop command
(stop at “open”)
FWD/REV run
selection
(FWD run at “open”,
REV run at “closed”)
2-10-15 Multifunction Output Function
Item name
Constant to be set
Factory preset
Multifunction output function
No. 34 and No. 35
Refer to page 41.
Functions of external output terminals 14 to 16, and 15 and 16 can
be switched.
Function of terminal 14 to 16: set into No. 34.
Function of terminal 15 and 16: set into No. 35.
Set value
Function
0 (see note)
In operation
1 (see note)
Frequency agreed
2
Zero speed
3
Frequency detection (output frequency
≥
frequency detection level)
4
Overtorque detected
2-10-16 Frequency/Current Meter Calibration
Item name
Constant to be set
Factory preset
Analog output gain
No. 45
1.00
analog output selection
No. 21
0000
Frequency/current meter connected to the inverter can be cali-
brated without using a resistor for calibration.
bn-11
+
--
FM
18
19
Frequency/current meter
(3 V 1 mA full scale)
No. 21 = xx0x
0: Output frequency meter
1: Output current meter
2-10-17 Overtorque Detection Function
Item name
Constant to be set
Factory preset
Overtorque detection level
No. 38
160%
Overtorque detection time
No. 39
0.1 s
Overtorque detection signal
No. 34 and No. 35
Refer to page 41.
Overtorque detection selection
No. 37
Refer to page 42.
Section 2-10
Summary of Contents for SYSDRIVE 3G3SV
Page 1: ...6 6 5 9 69 19 57 5 69 BB 69 BB 2SHUDWLRQ 0DQXDO...
Page 3: ...0 1 2 3...
Page 5: ...2 4 4 3 4 5 5 6 7 8 8...