Set Value = 1: Frequency Agreed
Detection width
2 Hz
Output frequency
Frequency agreed signal
Release width
4 Hz
Frequency
reference
Closed
Set Value = 3: Set Value or More
Output frequency
Frequency detection signal
Release width
--2 Hz
Closed
No. 36
2-10-20 S-curve at Accel/Decel Time
Item name
Constant to be set
Factory preset
S-curve at accel/decel time
No. 21
0000
The S-curve characteristics of the soft starter depend on the set-
ting of digits 1 and 2 as follows:
(Digit 4
Digit 3)
0
1:
The S-curve characteristics is 0.2 s.
0
0:
No S-curve characteristics
1
0:
The S-curve characteristics is 0.5 s.
1
1:
The S-curve characteristics is 1 s.
Output frequency
S-curve characteristics
time(TSC)
Frequency ref.
Time
Note
S-curve characteristics time refers to the time from acceleration
rate 0 to the time when a normal acceleration rate determined by a
specified acceleration time is obtained.
1, 2, 3...
1. Time chart at FWD/REV run change with S-curve characteris-
tics
Digit 3, Digit 4 (S-curve
Selection of Soft
Starter)
Section 2-10