(
The figure below shows the time chart at FWD/REV run change
during deceleration and stop.
FWD RUN command
REV RUN command
Output frequency
Min. output frequency
No-07
Acceleration
Deceleration
DC injection braking
time stopping
No-27
Min. output
frequency
No-07
Acceleration
Deceleration
: S-curve characteristic
Note
When digits 3 and 4 are 00, no S-curve characteristics at comple-
tion of deceleration.
2. Time chart at FWD/REV run change without S-curve charac-
teristics
The figure below shows the time chart at FWD/REV run change
during deceleration and stop.
FWD RUN command
REV RUN command
Output frequency
Min. output frequency
No-07
Acceleration
Deceleration
DC injection braking
time at stopping
No-27
Min. output
frequency
No-07
Acceleration
Deceleration
2-10-21 Momentary Power Loss Protection
Item name
Constant to be set
Factory preset
Operation continued at momentary power loss
No. 46
0000
Digit 1 = 0: When momentary stop is detected, power failure (UV
fault) occurs and the inverter output is shut off.
Digit 1 = 1: If momentary stop time is within momentary assurance
time (see note), the operation continues after the momentary stop.
If the momentary assurance time is exceeded, the inverter output
is shut off.
Note
0.75 kW max.: Approximately 1 s.
1.5 kW max.:
Approximately 2 s.
2-10-22 No. of Auto Reset/Restart Operation (No. 47)
Set the number of auto reset/restart operation. Setting of zero
causes no auto reset/restart operation.
Operation Continued
at Momentary Stop
Section 2-10
Summary of Contents for SYSDRIVE 3G3SV
Page 1: ...6 6 5 9 69 19 57 5 69 BB 69 BB 2SHUDWLRQ 0DQXDO...
Page 3: ...0 1 2 3...
Page 5: ...2 4 4 3 4 5 5 6 7 8 8...