9 Quick-response Inputs
9-3
CP2E CPU Unit Software User’s Manual(W614)
9
-1 Quic
k-resp
ons
e Inp
u
ts
9
9-1-2 Flo
w of
Operation
Precautions for Correct Use
Precautions for Correct Use
A built-in input cannot be used as a quick-response input if it is being used as a normal input,
interrupt input, or high-speed counter input. Refer to
Allocating Built-in Input Terminal
for
details.
Click the Built-in Input Tab and select
Quick
in the interrupt input settings.
Built-in Input Tab Page
9-1-2
Flow of Operation
1
•
Set IN2 to IN9 for quick-response inputs on the Built-in Input
Tab Page of the PLC Setup using the CX-Programmer.
•
The terminals 02 to 09 of CIO 0 can be used for quick-
response inputs. Bits CIO 0.02 to CIO 0.09 correspond to ter-
minals 02 to 09.
2
Read the status of CIO 0.02 to CIO 0.09 using the LD instruction
or other instructions.
PLC Setup
Quick-response input setting
Corresponding bit address
IN2
Select
Quick
for IN2
to IN9.
CIO 0.02
IN
3
CIO 0.0
3
IN4
CIO 0.04
IN5
CIO 0.05
IN6
CIO 0.06
IN7
CIO 0.07
IN
8
CIO 0.0
8
IN9
CIO 0.09
PLC Set
u
p
Create ladder
program
Cyclic task or
interr
u
pt task
S
elect
Q
u
ick
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......