11-3
11 High-speed Counters
CP2E CPU Unit Software User’s Manual(W614)
11
-1 Over
vie
w
11
1
1-1-2
Flo
w
of Oper
ation
Precautions for Correct Use
Precautions for Correct Use
A built-in input cannot be used as a normal input, interrupt input, or quick-response input if it is
being used as a high-speed counter input. Refer to
Allocating Built-in Input Terminal
for
details.
Click the Built-in Input Tab and select the
Use high speed counter
Check Box for high-speed counters
0 to 5. Set the counting mode, reset method, and input setting.
11-1-2 Flow of Operation
1
•
Enable the required high-speed counters.
•
Select the
U
s
e high
s
peed counter
Check Box for high-
speed counters 0 to 5. Set the input setting, counting
mode and reset method on the Built-in Input Tab Page of
the PLC Setup using the CX-Programmer.
•
Terminals 00 to 06 on the CIO 0 terminal block can be
used for high-speed counters. High-speed counters 0 to
5 correspond to terminals 00 to 06.
2
•
Read the PV from Auxiliary Area or by executing a PRV
instruction.
•
Execute a PRV instruction.
PLC Setup
PLC Set
u
p
Read co
u
nter PV
Create
ladder
program
Read co
u
nter fre
qu
ency
Summary of Contents for SYSMAC CP Series
Page 3: ......
Page 32: ...1 Overview 1 4 CP2E CPU Unit Software User s Manual W614 ...
Page 44: ...3 CPU Unit Operation 3 8 CP2E CPU Unit Software User s Manual W614 ...
Page 116: ...6 I O Allocation 6 8 CP2E CPU Unit Software User s Manual W614 ...
Page 144: ...7 PLC Setup 7 28 CP2E CPU Unit Software User s Manual W614 ...
Page 170: ...10 Interrupts 10 14 CP2E CPU Unit Software User s Manual W614 ...
Page 200: ...11 High speed Counters 11 30 CP2E CPU Unit Software User s Manual W614 ...
Page 272: ...12 Pulse Outputs 12 72 CP2E CPU Unit Software User s Manual W614 ...
Page 278: ...13 PWM Outputs 13 6 CP2E CPU Unit Software User s Manual W614 ...
Page 460: ...18 Programming Device Operations 18 28 CP2E CPU Unit Software User s Manual W614 ...
Page 576: ...Revision 2 CP2E CPU Unit Software User s Manual W614 ...
Page 577: ......