Hardware reference
HARDWARE REFERENCE MANUAL
125
Revi
si
on 3.0
Slave address settings:
Set the slave address with pins 1 to 5 on the dipswitch on the front
of the distributed I/O module.
Refer to the following table, and set the slave addresses as
required.
/i
Pin no.
Setting
Function
1 to 5
on
Set the slave address of pins 1 through 5. For details, refer to
the table below:
off
6
on
32-byte data transmission (MECHATROLINK-II).
7
on
The output when communication stops is set to “data immedi-
ately before stop“.
off
The output when communication stops is set to “0“.
8
on
Sets the baud rate to 10 Mbps.
Pin No.
Slave address
1
2
3
4
5
0
0
0
0
0
Not used
1
0
0
0
0
1
0
1
0
0
0
2
1
1
0
0
0
3
0
0
1
0
0
4
1
0
1
0
0
5
0
1
1
0
0
6
1
1
1
0
0
7
0
0
0
1
0
8
1
0
0
1
0
9
0
1
0
1
0
10
1
1
0
1
0
11