Run Command
Output Frequency
ON
OFF
DC Injection Braking
Time at Stop
(b2-04)*
Minimum Baseblock Time (L2-03)
DC Braking
Current (b2-02)
DC Injection Braking
Motor Speed
Figure 5.6 DC Injection Braking to Stop
The time for DC Injection Braking is determined by the value set to b2-04 and by the output frequency at the time the Run
command is removed. It can be calculated by:
=
DC Injection brake time
b2-04 • 10 • Output frequency
Max. output frequency (E1-04)
Output frequency when
Stop command was entered
100%
(Maximum output
frequency)
10%
DC Injection braking time
b2-04× 10
b2-04
Figure 5.7 DC Injection Braking Time Depending on Output Frequency
Note:
If an overcurrent (oC) fault occurs during DC Injection Braking to stop, lengthen the minimum baseblock time (L2-03) until the fault no
longer occurs.
Setting 3: Coast to Stop with Timer
When the Run command is removed, the drive will turn off its output and the motor will coast to stop. If a Run command
is input before the operation wait time
t
expires, the drive will not rotate the motor and the Run command will need to be
cycled before operation can occur.
Operation Wait Time
t
Run Command
Output Frequency
ON
ON
ON
OFF
OFF
Drive output voltage
interrupted
Figure 5.8 Coast to Stop with Timer
The operation wait time
t
is determined by the output frequency when the Run command is removed and by the active
deceleration time.