Predefined V/f Patterns for 4.0 to 15.0 kW Drives
The following graphs are for 200 V class drives. Double values when using a 400 V class drive.
Table 5.20 Rated Torque Characteristics, Settings 0 to 3
Setting = 0
50 Hz
Setting = 1
60 Hz
Setting = 2
60 Hz
Setting = 3
72 Hz
0
7
200
1.3 2.5
50
14
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
60
V
oltage (V)
Frequency (Hz)
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
60
50
0
7
14
200
1.5 3
72
60
V
oltage (V)
Frequency (Hz)
Table 5.21 Derated Torque Characteristics, Settings 4 to 7
Setting = 4
50 Hz
Setting = 5
50 Hz
Setting = 6
60 Hz
Setting = 7
60 Hz
V
oltage (V)
Frequency (Hz)
0
6
200
1.3
25
50
35
0
7
200
1.3
25
50
50
V
oltage (V)
Frequency (Hz)
V
oltage (V)
Frequency (Hz)
0
6
200
1.5
30
60
35
0
7
200
1.5
30
60
50
V
oltage (V)
Frequency (Hz)
Table 5.22 High Starting Torque, Settings 8 to B
Setting = 8
50 Hz
Setting = 9
50 Hz
Setting = A
60 Hz
Setting = B
60 Hz
0
9
200
1.3 2.5
50
18
V
oltage (V)
Frequency (Hz)
V
oltage (V)
Frequency (Hz)
0
11
200
1.3 2.5
50
23
V
oltage (V)
Frequency (Hz)
0
9
200
1.5 3
60
18
0
13
200
1.5 3
60
23
V
oltage (V)
Frequency (Hz)
Table 5.23 Constant Output, Settings C to F
Setting = C
90 Hz
Setting = D
120 Hz
Setting = E
180 Hz
Setting = F
60 Hz
0
7
14
200
1.5 3
90
60
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
120
60
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
180
60
V
oltage (V)
Frequency (Hz)
V
oltage (V)
Frequency (Hz)
0
7
14
200
1.5 3
60
Setting a Custom V/f Pattern
Setting parameter E1-03 to “F” allows to set up a custom V/f pattern by changing parameters E1-04 to E1-13.
When E1-03 is changed to “F”, the default values for parameters E1-04 to E1-13 will be equal to V/f pattern 0 of the
predefined patterns.
n
V/f Pattern Settings E1-04 to E1-13
Using parameters E1-04 through E1-13, the user can either monitor the V/f pattern values if E1-03 =< 15 or set up a custom
V/f pattern as shown in
Figure 5.40
when E1-03 = F.
No.
Parameter Name
Setting Range
Default
E1-04
Maximum Output Frequency
40.0 to 400.0 Hz
<1>
,
<2>
E1-05
Maximum Voltage
0.0 to 255.0 V
<3>
<1>
,
<2>
E1-06
Base Frequency
0.0 to 400.0 Hz
<1>
,
<2>
E1-07
Middle Output Frequency
0.0 to 400.0 Hz
<1>
E1-08
Middle Output Frequency Voltage
0.0 to 255.0 V
<3>
<1>
E1-09
Minimum Output Frequency
0.0 to 400.0 Hz
<1>
,
<2>
E1-10
Minimum Output Frequency Voltage
0.0 to 255.0 V
<3>
<1>
E1-11
Middle Output Frequency 2
0.0 to 400.0 Hz
0.0 Hz
E1-12
Middle Output Frequency Voltage 2
0.0 to 255.0 V
<3>
0.0 V
5.5 E: Motor Parameters