Setting 0: User Defined Setting
Setting 1: BOOTP
Setting 2: DHCP
n
F7-14: Ethernet Duplex Mode Selection
Sets the duplex mode for Ethernet communications.
No.
Parameter Name
Setting Range
Default
F7-14
<1>
Duplex Mode Selection
0 to 2
0
<1> Valid from drive software version 1011 and later. Parameter number was F7-15 in older software.
Setting 0: Auto Negotiate
Setting 1: Half Duplex Forced
Setting 2: Full Duplex Forced
n
F7-15: Ethernet Communication Speed Selection
Sets the duplex mode for Ethernet communications.
No.
Parameter Name
Setting Range
Default
F7-15
<1>
Communication Speed Selection
0, 10, 100
0
<1> Valid from drive software version 1011 and later. Parameter number was F7-18 in older software.
Setting 0: Auto Detection
Setting 10: 10 Mbps
Setting 100: 100 Mbps
n
F7-16: Ethernet Communication Loss Time Out
Sets the communication loss time out value.
No.
Parameter Name
Setting Range
Default
F7-16
<1>
Communication Loss Time Out
0 to 300
0
<1> Valid from drive software version 1011 and later. Parameter number was F7-21 in older software.
n
F7-17 to F7-22: EtherNet Scaling Factors
These parameters define scaling factors for drive monitors in the EtherNet Class ID 2AH - AC Drive Object.
No.
Parameter Name
Setting Range
Default
F7-17
<1>
EtherNet Speed Scaling
-15 to 15
0
F7-18
<1>
EtherNet Current Scaling
-15 to 15
0
F7-19
<1>
EtherNet Torque Scaling
-15 to 15
0
F7-20
<1>
EtherNet Power Scaling
-15 to 15
0
F7-21
<1>
EtherNet Voltage Scaling
-15 to 15
0
F6-22
<1>
EtherNet Time Scaling
-15 to 15
0
<1> Valid from drive software version 1011 and later.
Setting
The monitor value in the Class 2AH - AC Drive Object is calculated by:
Class 2AH Object Monitor = Drive Value x 2
Scaling
Example:
If the drive output frequency monitor (U1-02) is 50.0 and the scaling is set to F7-17 = 3, then the value in the Class 2AH
- AC Drive Object, Instance 1, Attribute 7 would be 500 x 2
3
= 4000.