E5: PM Motor Parameters
E5-01
<25>
Motor Code
Selection (for PM
motor)
Enter the Yaskawa motor code for the PM motor being
used. Various motor parameters are automatically set based
on the value of this parameter.
Note:
Set to FFFF when using a specialized or custom
motor. For all other motors:
0 0 0 0
0: 1800 r/min Series
1: 3600 r/min Series
2: 1750 r/min Series
3: 1450 r/min Series
4: 1150 r/min Series
F: Special Motor
Motor Voltage Class
and Capacity
0: Pico Motor
(SMRA Series)
1: Derated Torque for IPM
Motors
(SSR 1 Series)
All motor parameters are reinitialized to factory settings
when this parameter is set.
0000 to
FFFF
<12>
<38>
−
−
S
329
152
E5-02
<25>
Motor Rated
Capacity (for PM
motor)
Sets the rated capacity of the motor.
0.10 to 18.5
<10>
−
−
S
32A
152
E5-03
<25>
Motor Rated
Current
Sets the motor rated current in amps.
10 to 200%
of drive
rated
current
<27>
<4>
−
−
S
32B
152
E5-04
<25>
Motor Poles
Sets the number of motor poles.
2 to 48
<10>
−
−
S
32C
152
E5-05
<25>
Motor Resistance
Set the resistance for each motor phase in units of
0.001 Ω.
0.000 to
65.000
<10>
−
−
S
32D
153
E5-06
<25>
Motor d Axis
Inductance
Sets the d axis inductance in units of 0.01 mH.
0.00 to
300.00
<10>
−
−
S
32E
153
E5-07
<25>
Motor q Axis
Inductance
Sets the q axis inductance in units of 0.01 mH.
0.00 to
600.00
<10>
−
−
S
32F
153
E5-09
<25>
Motor Induction
Voltage Constant 1
Set the induced phase peak voltage in units of 0.1 mV (rad/
s) [electrical angle].
Set this parameter when using a Yaskawa SSR1 series PM
motor with derate torque, or a Yaskawa SST4 series motor
with constant torque.
When setting this parameter, E5-24 should be set to 0. An
alarm will be triggered if both E5-09 and E5-24 are set to
0, or if neither parameter is set to 0.
0.0 to
2000.0
<10>
−
−
S
331
153
E5-24
<25>
Motor Induction
Voltage Constant 2
Set the induced phase-to-phase rms voltage in units of 0.1
mV/(r/min) [mechanical angle].
Set this parameter when using a Yaskawa SMRA Series
SPM Motor.
When setting this parameter, E5-09 should be set to 0. An
alarm will be triggered if both E5-09 and E5-24 are set to
0, or if neither parameter is set to 0.
If E5-03 (Motor Rated Current) is set to 0, however, then
an alarm will not be triggered when both E5-09 and E5-24
are set to 0.
0.0 to
2000.0
0
<10>
−
−
S
353
153
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control.
<4> Default setting value is dependent on parameter A1-06. This setting value is 0 when A1-06 = 0, and 1 when A1-06 does not = 0.
<10> Default setting value is dependent on parameter E5-01, Motor Code Selection.
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<21> Range upper limit is dependent on parameter E4-01 Motor 2 Rated Current.
<22> Parameter can be changed during run.
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<25> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<26> Parameter ignored when E1-11, Motor 1 Mid Output Frequency 2, and E1-12, Motor 1 Mid Output Frequency Voltage 2, are set to 0.0.
<27> Setting units for this parameter are determined by o2-04, Drive Model Selection. Less than 11 kW: 2 decimal points, 11 kW and above: 1
decimal point.
<37> Setting range becomes 0.00 to 130.00 for drives 0.2 kW and smaller.
<38> If using a Yaskawa SMRA Series SPM Motor, the default setting is 1800 r/min.
<52> Parameter ignored when E3-11, Motor 2 Mid Output Frequency 2, and E3-12, Motor 2 Mid Output Frequency Voltage 2, are set to 0.
<53> Default setting depends on the control mode for motor 2 set in parameter E3-01. The given value is for V/f Control.
<57> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection.