No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
L8-05
Input Phase Loss Protection
Selection
Selects the detection of input current phase loss, power
supply voltage imbalance, or main circuit electrolytic
capacitor deterioration.
0: Disabled
1: Enabled
0,1
1
<56>
A A A
4B1
204
L8-07
Output Phase Loss
Protection
Selects the output phase loss detection.
0: Disabled
1: Enabled (triggered by a single phase loss)
2: Enabled (triggered when two phases are lost)
Output phase loss is detected when operating with less than
5% of the drive rated current. Detection can mistakenly occur
if the motor is too small relative to the drive capacity rating
(this parameter should be disabled in such cases).
0 to 2
1
A A A
4B3
204
L8-09
Output Ground Fault
Detection Selection
Selects the output ground fault detection.
0: Disabled
1: Enabled
0, 1
<12>
A A A
4B5
205
L8-10
Heatsink Cooling Fan
Operation Selection
Controls the heatsink cooling fan operation.
0: Fan On-Run Mode - Fan will operate only when the drive
is running and for L8-11 seconds after stop.
1: Fan always on - Cooling fan operates whenever the drive
is powered up.
0, 1
0
A A A
4B6
205
L8-11
Heatsink Cooling Fan
Operation Delay Time
This parameter sets the delay time for the cooling fan to shut
off after the run command is removed when L8-10 = 0.
0 to 300
60 s
A A A
4B7
205
L8-12
Ambient Temperature
Setting
Used to input the ambient temperature. This value adjusts the
drives oL2 detection level.
-10 to 50 40 °C A A A
4B8
205
L8-15
oL2 Characteristics Selection
at Low Speeds
Sets the oL2 characteristics at output frequencies below 6 Hz.
0: No oL2 level reduction below 6 Hz.
1: oL2 level is reduced linearly below 6 Hz. It is halved at 0
Hz.
0,1
1
A A A
4BB
205
L8-18
Soft CLA Selection
Selects the software current limit function. Typically no
adjustment is required.
0: Disabled
1: Enabled
0,1
1
A A −
4BE
205
L8-19
Frequency Reduction Rate
during oH Pre-Alarm
Specifies the frequency reference reduction gain at overheat
pre-alarm when L8-03 = 4.
0.1 to 1.0
0.8
A A A
4BF
204
L8-29
Current Unbalance Detection
(LF2)
Selects the detection of unbalanced output currents caused
by faulty devices in the output circuit.
0: Disabled
1: Enabled
0 to 1
1
− − A
4DF
206
L8-35
Installation Method
Selection
Selects the installation type:
0: IP20/Open-Chassis Drive
1: Side-by-Side Mounting
2: NEMA Type 1 Drive
3: Finless Drive or External Heatsink Installation
0 to 3
<12>
<25>
Α Α A 4ECH
206
L8-38
Carrier Frequency
Reduction
Provides protection to the IGBTs by reducing the carrier
frequency at low speeds.
0: Disabled
1: Enabled below 6 Hz
2: Enabled for the whole speed range
0 to 2
<12>
A A A
4EF
206
L8-40 Carrier Frequency Reduction
Time
Sets the time for that the drive continues running with
reduced carrier frequency after the carrier reduction
condition has gone (see also L8-38).
A setting of 0.00 s disables the carrier frequency reduction
time.
0.00 to
2.00
0.50 A A A
4F1
207
L8-41
High Current Alarm
Selection
Configures an alarm when the output current exceeds 150%
of the drive rated current.
0: Alarm disabled.
1: Alarm enabled.
0,1
0
A A A
4F2
207
<2> Default setting value is dependent on parameter A1-02, Control Method Selection. The value shown is for A1-02 = 0-V/f Control.
<7> Default setting value is 120% when C6-01 is set to 1 (ND) and 150% when C6-01 is set to 0 (HD).
<9> Default setting value is dependent on parameter E1-01, Input Voltage Setting.
<10> Default setting value is dependent on parameter E5-01, Motor Code Selection.
<12> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<24> Values shown here are for 200 V class drives. Double the value when using a 400 V class drive.
<25> Parameter setting value is not reset to the default value during drive initialization, A1-03 = 1110, 2220, 3330.
<29> Setting value 2 is not available A1-02 = 5-PM OLV Control. When enabled, the drive stops accelerating when it exceeds the value of L3-02,
Stall Prevention Level. The drive decelerates after 100 ms and begins accelerating again after restoring the current level.
<31> Use caution when working with regenerative loads as motor speed can exceed the frequency reference during overvoltage suppression function
operation. Set to "Disable" when motor speed needs to accurately match the frequency reference, and also when using a braking resistor. An
ov fault may still occur even when this function is enabled if there is a sudden increase in the regenerative load.
<50> The setting range depends on the control mode set in A1-02. For PM OLV Control the setting range is 0 to 2.
B.2 Parameter Table
326
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23