<51> Parameter value is changed if E2-11 is manually changed or changed by Auto-Tuning.
<56> The default value is 0 for all 200 V Single-Phase drives.
<57> Default setting value is dependent on parameter o2-04, Drive Model Selection and C6-01, Drive Duty Selection.
u
n: Advanced Performance Set-Up
The n parameters are used to adjust more advanced performance characteristics such as hunting prevention, speed feedback
detection, high-slip braking and R1 online tuning.
No.
Name
Description
Range
Def.
Control
Mode
Addr.
Hex
Pg.
V/f O
LV
P
M
n1: Hunting Prevention
Use n1 parameters to configure hunting prevention operation.
n1-01
Hunting Prevention
Selection
If the motor vibrates while lightly loaded, Hunting Prevention
may reduce the vibration.
0: Disabled
1: Enabled
When quick response is needed disable Hunting Prevention.
0,1
1
A − −
580
208
n1-02
Hunting Prevention Gain
Setting
Sets the gain for the Hunting Prevention Function.
If the motor vibrates while lightly loaded and n1-01 = 1,
increase the gain by 0.1 until vibration ceases.
If the motor stalls while n1-01 = 1, decrease the gain by 0.1
until the stalling ceases.
0.00 to
2.50
1.00 A − −
581
208
n1-03
Hunting Prevention Time
Constant
Sets the time constant used for hunting prevention.
0 to 500
<12>
A − −
582
208
n1-05
Hunting Prevention Gain
while in Reverse
Sets the gain used for Hunting Prevention.
When set to 0, the gain n1-02 is used for operation in reverse
direction.
0.00 to
2.50
0.00 A − −
530
208
n2: Speed Feedback Detection Control Function
Use n2 parameters to configure the Speed Feedback Detection Control function operation.
n2-01
Speed Feedback Detection
Control (AFR) Gain
Sets the internal speed feedback detection control gain in the
automatic frequency regulator (AFR).
This parameter does not typically require adjustment. Adjust
this parameter as follows:
If hunting occurs, increase the set value.
If response is low, decrease the set value.
0.00 to
10.00
1.00 − A −
584
208
Adjust the setting by 0.05 units at a time, while
checking the response.
n2-02
Speed Feedback Detection
Control (AFR) Time
Constant
Sets the AFR time constant 1.
0 to 2000 50 ms − A −
585
209
n2-03
Speed Feedback Detection
Control (AFR) Time
Constant 2
Sets the AFR time constant 2. Increase the setting if
overvoltage occurs during sudden load changes or the speed
overshoots during fast acceleration.
0 to 2000 750
ms
− A −
586
209
n3: High-Slip Braking
Use n3 parameters to configure the high-slip braking function.
n3-01
High-Slip Braking
Deceleration Frequency
Width
Sets the output frequency reduction step width when the drive
stops the motor using high-slip braking (HSB).
If Overvoltage (ov) faults occur during HSB, this parameter
may need to be increased.
1 to 20
5%
A − −
588
209
n3-02
High-Slip Braking Current
Limit
Sets the current limit during HSB. Higher n3-02 settings will
shorten motor stopping times but increase the motor current,
and therefore motor heating.
100 to 200 150% A − −
589
209
n3-03
High-Slip Braking Dwell
Time at Stop
Sets the time the drive will run with minimum frequency
(E1-09) at the end of deceleration.
If this time is set too low, the machine inertia can cause the
motor to rotate slightly after HSB completion.
0.0 to 10.0 1.0 s A − −
58A
210
n3-04
High-Slip Braking Overload
Time
Sets the time required for an HSB overload fault (oL7) to
occur when the drive output frequency does not change
during an HSB stop. This parameter does not typically require
adjustment.
30 to 1200 40 s A − −
58B
210
n3-13
Overexcitation Deceleration
Gain
Applies a gain to the V/f pattern during deceleration (L3-04
= 4). Returns to normal values after ramp to stop or at re-
acceleration.
To increase the braking power of overexcitation, increase the
gain by 1.25 to 1.30.
1.00 to
1.40
1.10 A A −
531
210
n3-21
High-Slip Suppression
Current Level
If overcurrent or overload occur during high-slip
deceleration, reduce the high-slip suppression current level.
Set as a percentage of the drive rated current.
0 to 150 100% A A −
579
210
n3-23
Overexcitation Operation
Selection
0: Enabled in both directions
1: Enabled only when rotating forward
2: Enabled only when in reverse
0 to 2
0
A A −
57B
210
B.2 Parameter Table
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
327
B
Parameter List