No.
Description
Unit
Setting Range
−
Model VZA
−
42P2
43P0
44P0
45P5
C6-01
Normal/Heavy Duty
−
HD
ND
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
−
95
96
97
99
E2-11
(E4-11,
T1-02)
Motor rated power
kW
2.2
3.0
3.0
3.7
4.0
5.5
5.5
7.5
b3-06
Speed Search current 1
−
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
Energy saving coefficient
−
313.6
265.7
265.7
245.8
245.8
189.5
189.5
145.38
C6-02
Carrier frequency
−
3
7
3
7
3
7
3
7
E2-01
(E4-01,
T1-04)
Motor rated current
A
4.2
5.7
5.7
7
7
9.8
9.8
13.38
E2-02
(E4-02)
Motor rated slip
Hz
3
2.7
2.7
2.7
2.7
1.5
1.5
1.3
E2-03
(E4-03)
Motor no-load current
A
1.5
1.9
1.9
2.3
2.3
2.6
2.6
4.0
E2-05
(E4-05)
Motor line-to-line resistance
Ω
6.495
4.360
4.360
3.333
3.333
1.595
1.595
1.152
E2-06
(E4-06)
Motor leakage inductance
%
18.7
19
19
19.3
19.3
18.2
18.2
15.5
E2-10
(E4-10)
Motor Iron Loss
W
77
105
105
130
130
193
193
263
E5-01
Motor Code
hex
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
Momentary power loss ride-
through time
s
0.5
0.5
0.5
0.5
0.5
0.5
0.8
0.8
L2-03
Momentary power loss Baseblock
time
s
0.5
0.5
0.5
0.6
0.6
0.7
0.7
0.8
L2-04
Momentary power loss voltage
recovery time
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L2-05
Uv detection voltage
V dc
380
380
380
380
380
380
380
380
L3-24
Motor acceleration time
s
0.145
0.145
0.145
0.154
0.154
0.154
0.168
0.175
L8-02
Overheat alarm level
°C
100
100
100
100
100
100
110
110
L8-09
Ground fault selection
−
0
0
0
0
0
0
1
1
L8-35
Installation Method Sel.
−
0
0
0
0
0
0
2
2
L8-38
Carrier frequency reduction
selection
−
1
1
1
1
1
1
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
10
10
10
B.5 Defaults by Drive Capacity (o2-04) and ND/HD (C6-01)
346
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
7/16/2008-13:23