No.
Description
Unit
Setting Range
−
Model VZA
−
47P5
4011
4015
C6-01
Normal/Heavy Duty
−
HD
ND
HD
ND
HD
ND
o2-04
Drive Model Selection
−
9A
9C
9D
E2-11
(E4-11,
T1-02)
Motor rated power
kW
7.5
11.0
11.0
15.0
15.0
18.5
b3-06
Speed Search current 1
−
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
Energy saving coefficient
−
145.38
140.88
140.88
126.26
126.26
115.74
C6-02
Carrier frequency
−
3
7
3
7
3
7
E2-01
(E4-01,
T1-04)
Motor rated current
A
13.3
19.9
19.9
26.5
26.5
32.9
E2-02
(E4-02)
Motor rated slip
Hz
1.30
1.70
1.70
1.60
1.60
1.67
E2-03
(E4-03)
Motor no-load current
A
4.0
5.6
5.6
7.6
7.6
7.8
E2-05
(E4-05)
Motor line-to-line resistance
Ω
1.152
0.922
0.922
0.550
0.550
0.403
E2-06
(E4-06)
Motor leakage inductance
%
15.5
19.6
19.6
17.2
17.2
20.1
E2-10
(E4-10)
Motor Iron Loss
W
263
385
385
440
440
508
E5-01
Motor Code
hex
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
Momentary power loss ride-
through time
s
1
1
2
2
2
2
L2-03
Momentary power loss Baseblock
time
s
0.8
0.9
0.9
1.0
1.0
1.0
L2-04
Momentary power loss voltage
recovery time
s
0.3
0.3
0.3
0.6
0.6
0.6
L2-05
Uv detection voltage
V dc
380
380
380
380
380
380
L3-24
Motor acceleration time
s
0.175
0.265
0.265
0.244
0.244
0.317
L8-02
Overheat alarm level
°C
110
110
110
110
110
110
L8-09
Ground fault selection
−
1
1
1
1
1
1
L8-35
Installation Method Sel.
−
2
2
2
2
2
2
L8-38
Carrier frequency reduction
selection
−
2
2
2
2
2
2
n1-03
Hunting Prevention Time Constant
ms
10
10
10
10
10
10
B.5 Defaults by Drive Capacity (o2-04) and ND/HD (C6-01)
SIEP C710606 20 OYMC AC Drive - V1000 User Manual
347
B
Parameter List
7/16/2008-13:23