Varispeed J7

353

Commom specifications

Model 

CIMR-J7AZ

#

Specifications

Co

ntrol funct

ions

Control method

Sine wave PWM (V/f control)

Output frequency range

0.1 to 400 Hz

Frequency tolerance

Digital reference: ±0.01% (–10 to +50 °C),

Analog reference: ±0.5% (25±10 °C)

Resolution of frequency set value

Digital reference: 0.01 Hz (less than 100 Hz), 0.1 Hz (100 Hz or more)

Analog reference: 1/1000 of max. output frequency

Resolution of output frequency

0.01 Hz

Overload capability

150% rated output current for one minute

Frequency set value

0 to 10 VDC (20 k

Ω

), 4 to 20 mA (250 

Ω

), 0 to 20 mA (250 

Ω

), frequency setting volume (selectable)

Accel/decel time

0.1 to 999 sex. (accel/decel time are independently programmed)

Braking torque

Short-term average deceleration torque

1

: 0.1, 0.2 kW (0.13 HP, 0,25 HP): 150% or more;

0.4/0.75 kW (0,5 HP, 1HP): 100% or more;

1.5 kW (2 HP): 50% or more;

2.2 kW (3 HP) or more: 20% or more

Continuous regenerative torque: Approx 20%

1.

Shows deceleration torque for uncoupled motor decelerating from 60 Hz with the shortest possible deceleration time.

V/f characteristics

Possible to program any V/f pattern

Functio

na

lity

Digital inputs

Four of the following input signals are selectable: forward/reverse run (3-wire sequence), fault reset, external fault (NO/NC 
contact input), multi-step speed operation, jog command, accel/decel time select, external baseblock (NO/NC contact input), 
speed search command, UP/DOWN command, accel/decel hold command, LOCAL/REMOTE selection, communication/
control circuit terminal selection, emergency stop fault, emergency stop alarm, self test

Digital outputs

Following output signals are selectable (NO/NC contact output): Fault, running, zero speed, speed agreed, 
frequency detection (output frequency 

≤  

or 

≥ 

set value), during overtorque detection, minor error, during baseblock, 

operation mode, inverter run ready, during fault retry, during undervoltage detection, reverse running, during speed search, 
data output through communication

Standard functions

Full-range automatic torque boost, slip compensation, 9-step speed operation (max.), restart after momentary power loss, 
DC injection braking current at stop/start (50% of inverter rated current, 0.5 sec, or less), frequency reference bias/gain, fault 
retry, speed search, frequency upper/lower limit setting, overtorque detection, frequency jump, accel/decel time switch, accel/
decel prohibited, S-curve accel/decel, frequency reference with built-in volume, constants copy (option) MEMOBUS commu-
nications (option)

Display

Status indicator LED: RUN and ALARM provided as standard LED’s

Digital operator: available to monitor frequency reference, output frequency, output current

Protec

ti

on 

Motor overload protection

Electronic thermal overload relay

Instantaneous overcurrent

Motor coasts to a stop at approx. 250% of inverter rated current

Overload

Motor coasts to a stop after 1 minute at 150% of inverter rated output current

Overvoltage

Motor coasts to a stop if DC bus voltage exceed 410 V  (double for 400 V class)

Undervoltage

Stops when DC bus voltage is approx. 200 V or less (double for 400 V class)

(approx. 160 V or less for single-phase series)

Momentary power loss

Following items are selectable: Nnot provided (stop if power loss is 15ms or longer), 

continuous operation if power loss is approx. 0.5 s or shorter, continuous operation

Cooling fin overheat

Protected by thermister

Stall prevention level

Individual level stall prevention can be set during acceleration or constant running, 

provided/not provided setting available during deceleration.

Cooling fan fault

Detected by electronic circuit (fan lock detection)

Ground fault

Protected by electronic circuit (operation level is approx. 250% of rated output current)

Power charge indication

ON until the DC bus voltage becomes 50 V or less, RUN lamp stays ON or digital operator LED stays ON. 

(Charge LED is provided for 400 V)

A

m

bi

e

n

t c

o

nditi

ons

Degree of protection

IP20

Cooling

Self cooling for 200 V 0,1..0,75 kW (single-phase) 0,1..0,4 kW (Three-phase) and for 400 V 0,2..0,75l kW

Cooling fan for 200 V (single-phase), 0.75 kW..4.0 kW (3-phase) and for 400 V 1,5..4.0 kW

Ambient temperature

-10 ºC to 50 ºC (non-freezing)

Ambient humidity

90% RH or less (non-condensing)

Storage temperature

-20 ºC..+60 ºC (short-term temperature during trasnportation)

Installation

Indoor (no corrosive gas, dust, etc.)

Installation height

Max. 1000 m

Vibration

10 to 20 Hz, 9.8 m/s

2

 max; 20 to 50 Hz, 2m/s

2

 max

Y203-EN2-02-Katalog.book  Seite 353  Mittwoch, 24. Mai 2006  2:22 14

Summary of Contents for VARISPEED J7 -

Page 1: ...analog output Optional RS 232C 485 communication Modbus PC Configuration tool CX drive CE UL and cUL marking Ratings 200 V class single phase 0 1 to 1 5 kW 200 V class three phase 0 1 to 4 0 kW 400 V...

Page 2: ...1 1 1 9 3 0 4 2 6 7 0 9 1 4 2 6 3 7 4 2 5 5 7 0 Rated output current A 0 8 1 6 3 5 8 11 17 5 1 2 1 8 3 4 4 8 5 5 7 2 9 2 Max output voltage V 3 phase 200 to 230 V proportional to input voltage Single...

Page 3: ...raking current at stop start 50 of inverter rated current 0 5 sec or less frequency reference bias gain fault retry speed search frequency upper lower limit setting overtorque detection frequency jump...

Page 4: ...s Selected function is lit see the functions below Its data is displayed on data display Operation key Press to run the motor The RUN light is ON while running Stop Reset key Press to stop the motor I...

Page 5: ...20P4 102 0 8 1 1 20P7 122 0 9 Fan cooled 1 5 21P5 2 108 129 96 118 1 3 2 2 22P2 154 1 5 4 0 24P0 140 161 128 2 1 200 V single phase 0 1 B0P1 1 68 128 70 56 118 5 0 5 Self cooled 0 2 B0P2 0 4 B0P4 112...

Page 6: ...E 169 111 50 135 156 91 5 3 M5 22 96 118 M4 3G3JV PFI3010 SE 169 111 50 135 156 91 5 3 M5 22 96 118 M4 3G3JV PFI3020 SE 174 144 50 135 61 120 5 M5 28 128 118 M4 Rasmi model Dimensions W H L X Y Invert...

Page 7: ...ZZ08122B CIMR J7AZ24P0 3G3IV PEZZ08122C Single phase 200 VAC CIMR J7AZB0P1 B0P2 B0P4 3G3IV PEZZ08122A CIMR J7AZB0P7 B1P5 3G3IV PEZZ08122B 3 phase 400 VAC CIMR J7AZ40P2 40P4 40P7 41P5 42P2 3G3IV PEZZ08...

Page 8: ...s 0 V common For a PNP transistor 24 V common a 24 V external power supply is necessary DC reactor option Forward run stop Reverse run stop External fault no contact Fault reset Multi step speed refer...

Page 9: ...8mA photocoupler isolation S2 Multi function input selection 2 Factory setting runs when CLOSED stops when OPEN S3 Multi function input selection 3 Factory setting fault reset S4 Multi function input...

Page 10: ...1 B0P2 B0P4 B0P7 B1P5 Inverter capacity kVA 0 3 0 6 1 1 1 9 3 0 Rated current A 0 8 1 6 3 0 5 0 8 0 Heat loss W Fin 3 7 7 7 15 8 28 4 53 7 Inside unit 10 4 12 3 16 1 23 0 29 1 Total heat loss 14 1 20...

Page 11: ...4 2 2 2 15 0 71 2 2 7 5 3 6 4 0 20 0 53 4 0 10 2 2 200 V class 400 V class Max applicable motor output kW Current value A Inductance mH Max applicable motor output kW Current value A Inductance mH 0...

Page 12: ...V 0 12 Kw 0 8 A CIMR J7AZB0P10 0 25 Kw 1 6 A CIMR J7AZB0P20 0 55 Kw 3 0 A CIMR J7AZB0P40 1 1 Kw 5 0 A CIMR J7AZB0P70 1 5 Kw 8 0 A CIMR J7AZB1P50 3x200 V 0 12 Kw 0 8 A CIMR J7AZ20P10 0 25 Kw 1 6 A CIMR...

Page 13: ...7 43P0 44P0 3G3JV PFI3020 SE 3G3JV PFI3020 E 20 15 1 0 Type Model Description Funtions Digital operator JVOP 146 Remote digital operator without potentiometer JVOP 144 Remote digital operator with pot...

Page 14: ...Description Installation Software CX drive Computer software Configuration and monitoring software tool for drives CX One Computer software Complete OMRON automation software including CX drive Type M...

Reviews: