XW5T
9
Grounding Terminal blocks Standard terminals
Note:
Use a conductive DIN Track when using a Grounding Terminal Block.
OMRON does not offer conductive DIN Tracks. Please use a commercially available product.
*1.
For the recommended applicable wire ranges, refer to page 17 for solid and stranded wires, and to page 19 for ferrules.
*2.
You can also use ferrules for 1.0 to 1.5 mm
2
wires if you use ferrules without insulation sleeve. Refer to page 19 for details.
Model
XW5G-P1.5-1.1-1
XW5G-P2.5-1.1-1
XW5G-P4.0-1.1-1
Appearance and internal
wiring
1 tier, 1:1
1 tier, 1:1
1 tier, 1:1
A
p
p
li
c
ab
le
w
ire
si
ze
s*
1
Stranded wire
0.08 mm
2
to 1.5 mm
2
0.14 mm
2
to 2.5 mm
2
0.2 mm
2
to 4.0 mm
2
Solid wire
0.14 mm
2
to 1.5 mm
2
0.14 mm
2
to 4.0 mm
2
0.2 mm
2
to 6.0 mm
2
Stranded wire with
ferrule with Plastic
sleeve
0.14 mm
2
to 0.75 mm
2
(1.5 mm
2
) *2
0.14 mm
2
to 2.5 mm
2
0.25 mm
2
to 4.0 mm
2
Dimensions
3.5 × 45 × 30.5
5.2 × 48.8 × 35.3
6.2 × 56.1 × 35.3
IEC rated voltage
500 V
800 V
UL rated voltage
600 V
Dielectric strength
1,890 VAC for 1 min
(leakage current: 1 mA max.)
2,000 VAC for 1 min
(leakage current: 1 mA max.)
End Cover
XW5E-P1.5-1.1-1
XW5E-P2.5-1.1-1
XW5E-P4.0-1.1-1
Special tool
XW4Z-00B
Applicable nameplates
XW5Z-P1.5LB
@
or commercially available
nameplate with 9.5 mm width and 0.5 mm
thickness
XW5Z-P2.5LB
@
or commercially available
nameplate with 9.5 mm width and 0.5 mm
thickness
XW5Z-P4.0LB
@
or commercially available
nameplate with 9.5 mm width and 0.5 mm
thickness