Troubleshooting
A-52
12.764 : PROFIBUS initialize error
Code
: &H000C &H02FC
Meaning/Cause
Initializing the PROFIBUS option board failed.
Action
Contact your distributor.
12.765 : PROFINET initialize error
Code
: &H000C &H02FD
Meaning/Cause
Initializing the PROFINET option board failed.
Action
Contact your distributor.
12.900 : Incorrect option setting
Code
: &H000C &H0384
Meaning/Cause
a. Error occurred in ID setting on the option module.
b. Option modules that cannot be mixed were installed.
c. The installed option module cannot be identified.
Action
a. Check the ID setting of the option module.
b. Install the correct option modules.
c. Replace the option module.
• Replace the controller.
12.901 : PIO internal error
Code
: &H000C &H0385
Meaning/Cause
a. The PIO board cable is abnormal.
b. The PIO board power is turned off, or has stopped operation.
c. The PIO board is breakdown.
Action
a. Check for a break disconnection, wiring error, short circuit on the PIO cable or the specifications
(cable length, etc.).
b. Check if power for the PIO board is supplied normally.
c. Replace the PIO board.
12.903 : PIO option setting error
Code
: &H000C &H0387
Meaning/Cause
The PIO board installed incorrectly.
Action
• Remove the PIO board for correct configuration.
• Set the PIO board INVALID for correct configuration.
12.904 : SIO option board initialize error
Code
: &H000C &H0388
Meaning/Cause
Initializing the SIO option board failed.
Action
Contact your distributor.
12.905 : Option board overlapped
Code
: &H000C &H0389
Meaning/Cause
The installed option board cannot be overlapped.
Action
Remove the option board that cannot be overlapped.
Summary of Contents for YRCX Series
Page 1: ...7 6HULHV DW 1R 1 5 5RERW RQWUROOHU 23 5 7 21 0 18 6 5 5RERWV 5 6HULHV...
Page 2: ......
Page 10: ......
Page 12: ......
Page 14: ......
Page 20: ......
Page 28: ......
Page 164: ......
Page 166: ......
Page 178: ......
Page 186: ......
Page 264: ......
Page 265: ......
Page 266: ...DW 1R 1 XWKRUL HG LVWULEXWRU 3ULQWHG LQ XURSH...