192
S
E
CT
IO
N 6
Term
inal
Block
Z550
Operation Manual
SECTION 6
Communication with External Devices
In the Case of Judgment output B
The judgment results for OUT0 to OUT7 (OK or NG) are output to DO0 to DO7.
All output terminals turn off when the mode is switched to a mode other than Run.The initial signal of
the output terminals is off. The terminals, however, may turn on for approximately 0.5 seconds when
the power supply is turned on.Make sure that these outputs are not treated as actual signals by
external devices.
Refer to Timing Charts for details on I/O timings.
p.222
Output data
Output terminals
Remark
OUT0 OK/NG
DO0
OK (PASS): Turns off
NG (HIGH, LOW, ERROR): Turns on
OUT1 OK/NG
DO1
OUT2 OK/NG
DO2
OUT3 OK/NG
DO3
OUT4 OK/NG
DO4
OUT5 OK/NG
DO5
OUT6 OK/NG
DO6
OUT7 OK/NG
DO7
(Not used)
DO8 to DO15
(Not used)
ALL-PASS DO16
Turns on if the results of all the registered outputs are PASS.This
can be used for comprehensive judgment.Note that the off delay
does not function for this output.
ERROR
DO17
Turns on if the judgment result of at least one of the registered
outputs is ERROR.This can be used to identify that an error has
occurred.Note that the off delay does not function for this output.
RUN
DO18
Turns on during measurement.Turns off while the scene is
changed or set.
BUSY
DO19
Turns on from the start of the measurement to the completion of
the profile data output if [Meas mode] is set to [Trg (External)] or
[Trg (RS-232C)].
operation.book Page 192 Monday, June 6, 2005 10:19 AM