Programmable Relay
ZEN V2 Units
11
■
Output Specifications (CPU Units and Expansion I/O Units)
Units with Relay Outputs
Units with Transistor Outputs
Item
Specifications
Circuit drawing
Maximum switching capacity
250 VAC/8 A (resistive load: cos
φ
= 1)
24 VDC/5 A (resistive load)
Use the following values for the total of all outputs.
CPU Units with 10 I/O points: 20 A max.
(15 A max. for Communications-type CPU Units)
CPU Units with 20 I/O points: 40 A max.
Expansion I/O Units:
20 A max.
Minimum switching capacity
5 VDC/10 mA (resistive load)
Relay life
Electrical
Resistive load: 50,000 times (cos
φ
= 1)
Inductive load: 50,000 times (cos
φ
= 0.4)
Mechanical
10 million times
ON response time
15 ms max.
OFF response time
5 ms max.
Item
Specifications
Circuit drawing
Maximum switching capacity
24 VDC +20%, 500 mA
Each circuit is configured with an independent common
circuit
Leakage current
0.1 mA max.
Residual voltage
1.5 V max.
ON response time
1 ms max.
OFF response time
1 ms max.
Q0 to Q3/OUT0 to OUT3
Q4/Q6
COM
Q5/Q7
Models with
20 I/O points
only
L
L
L
Internal
circuit
1,000
300
100
10
0
2
4
6
8
10
Contact current (A)
30
50
500
250-VAC resistive load
24-VDC resistive load/
250-VAC inductive load
24-VDC inductive load
(t = 7 ms)
Life (
×
10
3
)
The life under the worst conditions, of the output contacts used in
ZEN relay outputs is given in the above table. Guidelines for the
normal life of the relays are shown in the diagram on the right.
Life-test Curve (Reference Value)
Usage: 360 times/hour
Note:
The switching capacity, switching durability, and applicable
load area when actually using the relay depend on the type of
load, environmental conditions, and switching conditions.
Therefore, be sure to confirm these conditions for the actual
machine before use.
Q0 to Q3/OUT0 to OUT3
Models with
20 I/O points
only
390
Ω
COM
Q4/Q6
Q5/Q7
28.8 VDC max.
28.8 VDC max.
L
L
L
L
1 k
Ω
+
Internal
circuit