12
Programmable Relay
ZEN V2 Units
Connections
■
Input Connections
Units with AC Power Supply
Note: 1.
Supply power to both the CPU Unit and Expansion I/O Units from the same power supply and turn them ON and OFF at the same time.
2.
The input circuit commons for CPU Units with AC power supply are internally connected to the N terminal of the power supply circuit.
Wire the L terminal to the power supply of the input device.
3.
The input circuit commons for Expansion I/O Units with AC power supply are internally connected to the N terminal of the power supply
circuit. Wire the L terminal to the power supply of the input device.
CPU Units with 10 I/O Points and Expansion I/O Units
CPU Units with 20 I/O Points and Expansion I/O Units
Connecting Expansion I/O Units with DC Inputs
Note:
When connecting Expansion I/O Units with DC inputs to a CPU Unit with an AC power supply, the burst noise immunity will be 1 kV
(IEC 61000-4-4).
L
N
IN0 IN1 IN2 IN3
L
N
NC
I0
I1
I2
I3
I4
I5
100 to 240 VAC, 50/60 Hz
L
N
Circuit
protector
Input device
CPU Unit with 10 I/O points
ZEN-8E1AR Expansion
I/O Unit (AC input type)
L
N
NC
I0
I1
I2
I3
I4
I5
NC
I6
I7
I8
I9
Ia
Ib
L
N
IN0 IN1 IN2 IN3
L
N
Circuit
protector
CPU Unit with 20 I/O points
ZEN-8E1AR
Expansion I/O Unit
(AC input type)
100 to 240 VAC, 50/60 Hz
Input device
L
N
NC
I0
I1
I2
I3
I4
I5
COM IN0 IN1 IN2 IN3
COM IN0 IN1 IN2 IN3
L
N
CPU Unit with 10 I/O points
100 to 240 VAC, 50/60 Hz
DC power supply
Circuit
protector
Input
device
ZEN-8E1DR
Expansion I/O Unit
(DC inputs and
relay outputs)
Input
device
ZEN-8E1DT
Expansion I/O Unit
(DC inputs and
transistor outputs)