Section 4
Linear Input/Output
4-7
ZS-L
User’s Manual
Input Signal Settings
You can now set which of ON or OFF is set to an active state for each of the input wires.
FUN mode-[I/O SET]-[IN]
I/O Assignment Settings
■
Switching the bank by external signal input
You can select the function to be assigned to external input signals IN0 to IN3 from two
patterns,
• If you use SmartMonitor ZS, you can change the function assignments of IN2 and IN3 if [BANK] is
selected. For details, refer to the Help for SmartMonitor ZS.
• These settings are stored in each bank and must be set separately for each bank.
FUN mode-[I/O SET]-[I/O SET]-[IN]
For bank inputs A and B, the bank can be selected in the following combinations.
• Bank switching is begun 0.5 seconds after the input state changes.
• At most it takes about 30 seconds to switch banks.
• During bank switching the BUSY output becomes ON.
Setting
Description
IN0
IN1
IN2
IN3
OFF
The input wire is regarded as active when it is OFF.
ON
The input wire is regarded as active when it is ON.
Setting
Description
STAND
Select this to use external input function as in standard applications so
far.(default value)
IN0
IN1
IN2
IN3
External trigger
(timing) input
Reset input
LD-OFF input
Zero reset input
Bank
Select this to switch banks using external inputs.
IN0
IN1
IN2
IN3
Bank input A
Bank input B
LD-OFF input
Zero reset input
Bank to be Selected
Bank input A
Bank input B
BANK1
OFF
OFF
BANK2
OFF
ON
BANK3
ON
OFF
BANK4
ON
ON
Summary of Contents for ZS-L -
Page 1: ...USER S MANUAL Smart Sensor ZS L Series Ver 2 0 Cat No Z208 E1 02 ...
Page 52: ...2 24 Section 2 INSTALLATION CONNECTION ZS L User s Manual Section 2 SmartMonitor ZS ...
Page 90: ...3 38 Section 3 SETUP ZS L User s Manual Section 3 Setting the System Environment MEMO ...
Page 156: ...6 46 Section 6 APPENDIX ZS L User s Manual Section 6 INDEX ...
Page 158: ......