Installation
Unpacking and Placement
20
ONEAC CDR45I Series Power Conditioner, Installation Guide, 913-521 Rev. A
conditioner's output voltage may run a few volts higher than the rated
voltage until the load is switched on.
If the operating voltage matches that suggested by the equipment
manufacturer, turn OFF the main input and output circuit breakers on the
power conditioner, connect your equipment to the output power block, and
turn ON the main input circuit breaker followed by the main output circuit
breaker. Your equipment can now be turned ON and operated as usual
If voltage variations greater than the manufacturer's specifications exist on
any phase, a tap selection for that phase may be made to adjust the voltage
level (see
“Voltage Tap Selection and Range Change” on page 51
).
If there is
power
at the input with
no power
at the output:
1
Turn OFF the main output and input circuit breakers.
2
Turn OFF the main power source supplying the power conditioner.
3
Follow the procedure in
“Troubleshooting an Installation” on page 49
.
Unpacking and Placement
Your ONEAC CDR45I Series Power Conditioner is delivered on a wooden
pallet. Upon arrival, inspect the unit and pallet for signs of damage. The pallet
has two types of shipping indicators (tip and drop). Check these indicators for
signs of shipping stress.
In case you encounter an activated tip or drop sensor or any visible damage
proceed as follows:
1
Make a note on the delivery receipt and inspect for damage.
2
Leave in original container and packaging and request immediate inspection
from carrier within 3 days.
3
Collect the following information and inform SSTD about the incident:
– Name of the carrier
– Shipment information
– Pictures showing the damage
– Detailed report explaining the damage
4
Keep all sensors and packaging material for further investigations.
Summary of Contents for CDR45I Series
Page 6: ...Safety Information 6 ONEAC CDR45I Series Power Conditioner Installation Guide 913 521 Rev A...
Page 10: ...List of Figures 10 ONEAC CDR45I Series Power Conditioner Installation Guide 913 521 Rev...
Page 40: ...Physical Views 40 ONEAC CDR45I Series Power Conditioner Installation Guide 913 521 Rev A...