Installation
Output Connections
30
ONEAC CDR45I Series Power Conditioner, Installation Guide, 913-521 Rev. A
Figure 8
Position of the output connections
Conduits
The landing area can be fitted with up to five conduits landing points, and up to
51 mm (2 inch) diameter conduits. Knockout scribe points are located on the
back side of the conduit landing cover plate for your convenience.
Convenience Receptacles
Convenience receptacles are located on the back of the conditioner. Three (3)
IEC320 outlets are provided and rated at 208Vac,10 A maximum for all three.
Two (2) separate NEMA 5-15R duplex receptacles are provided and rated at
120 Vac, 15 A maximum for each duplex. These NEMA style receptacles are
shipped covered by a panel for compliance with the EU's low voltage directive.
Each convenience circuit is circuit breaker protected. The convenience
receptacles can be energized by their individual circuit breakers once the main
input circuit breaker is turned ON.
Output power block
Conduit landing
Convenience
Receptacle Circuit
Breakers
CPC connector –
external EMO and
auxiliary contacts
Three IEC-320
receptacles, 208 Vac,
total 10 A max
Two duplex NEMA
5-15R receptacles,
120 Vac, 15 A max,
each (Behind cover)