Maintenance
Cleaning
34
ONEAC CDR45I Series Power Conditioner, Installation Guide, 913-521 Rev. A
Cleaning
The power conditioner is painted with a textured paint to minimize noticeable
dirt and fingerprints. The outside may be wiped clean with a slightly damp
cloth.
Fuse Replacement
The ONEAC CDR45I Series Power Conditioners require fuses in some
locations. In the unlikely event that a fuse needs to be replaced, spare fuses have
been provided in the internal spares compartment behind the middle front panel
which covers the EMO transformer and the power terminal block.
All fuses are service personnel replaceable only. Since all fuses are located
behind secured panels and/or covers limiting access to hazardous voltages, only
qualified electricians should replace them. The fuse locations and specifications
are as follows:
Follow lock out recommendations described in
“Installation Overview” on
page 17
(step 3).
Table 6
Fuse locations and specifications
Location
Input
Fuse current
rating
Sources
Part numbers
Emergency OFF
Primary (2)
600 Vac
2 Amp
Littelfuse
KLDR2
Bussmann
LP-CC-2
Gould
ATDR2
Secondary (1)
250 Vac
1 Amp
Littelfuse
FLM-1
Bussman
FNM-1
Summary of Contents for CDR45I Series
Page 6: ...Safety Information 6 ONEAC CDR45I Series Power Conditioner Installation Guide 913 521 Rev A...
Page 10: ...List of Figures 10 ONEAC CDR45I Series Power Conditioner Installation Guide 913 521 Rev...
Page 40: ...Physical Views 40 ONEAC CDR45I Series Power Conditioner Installation Guide 913 521 Rev A...