CDR45I Specifications
Specifications
ONEAC CDR45I Series Power Conditioner, Installation Guide, 913-521 Rev. A
43
Normally open contacts. A single pair of normally open contacts are provided
whose coil is de-energized if the EMO contact circuit is opened. The normally
open contacts are accessed at pins J1-1 and J1-2 of the CPC connector.
Indicator lights
Green LED for incoming Input Power ON or power applied to the conditioner.
Green LED for Output Power ON or power applied to the main output power
block.
Forward transfer impedance
< 0.5 Ohms @ 1 KHz, L-N
< 0.05 Ohms @ 50/60 Hz L-N
Efficiency at rated load
> 97% @ 50 Hz.
Heat loss @ 80% of rated load
1170 watts (4000 BTU/hr.).
Load regulation response time
< 2 msec for a 50% change in load.
Surge Voltage withstand
ANSI/IEEE C62.41: Category A, 6 kV, 200 A 100 kHz ringwave, And
Category B, 6 kV, 500 A 100 kHz ringwave and 3000 A impulse.
Surge voltage let-thru
With unit under power, ANSI/IEEE C62.41 Category A 6 KV, 200 A. 100 kHz
ringwave surge applied yields < 10 V normal mode (L-N) and < 0.5 V common
mode (N-PE) at the output power block.
Overload capability
Can typically tolerate 10 times rated output for 0.5 cycle, 5.5 times rated output
for 1 second, and 3.5 times rated output for 5 seconds without degradation.
Magnetic stray field operating
< 5 Gauss (0.5 mTesla) anywhere on the conditioner’s surface for frequencies
less than or equal to 198 Hz under full rated load current into resistive load.
(Actual measurements indicate that < 1 Gauss peak except immediately above
the fans where < 3 Gauss peak.
Magnetic stray field non operating
< 2 mGauss (0.2
µ
Tesla) anywhere around conditioner. Measured at a distance
of 2.1m from conditioner. (IATA-Limit)
Operating temperature
0 ˚C to +40 ˚C
Storage temp
–40 ˚C to +70 ˚C
Elevation
3,000 meters (10,000 ft.) max.
Relative humidity
80% @ 30 ˚C
Qualified for 48 hours in 91% to 95% RH @ 25 ˚C (as per EN60950)
Qualification test, non operating
12 hours at 65 ˚C and 90% RH
Cooling
Forced air cooled