Battery Disposal
The typical battery life cycle is 3 to 5 years, at an ambient temperature of 25 °C, but is also dependent on
the frequency and duration of mains failures.
Once the battery has reached the end of its useful life, follow the procedure for battery replacement, see
“Replacing Batteries” on page 16.
After the batteries are replaced, a certified disposal/recycling company should carry out disposal/
recycling of the used batteries.
Exhausted rechargeable batteries are classified as “harmful toxic waste” and as such the law demands that
they be disposed of/recycled by an authorized recycling center.
The manufacturer’s service center is fully equipped to deal with such batteries, in accordance with the law
and with the greatest respect for the environment. Contact Technical Support to arrange for maintenance
and/or battery replacement. See page 1 for contact information.
Interfaces
The UPSs are equipped with a serial interface COM 3 and an interface slot COM.
These interfaces can be used for:
• Direct communication between UPS and a workstation/server.
• Integration of the UPS as client into a network with centralized monitoring via a ManageUPS
NET
SNMP adapter in the slot COM.
• Transfer of operational states to external alarm systems via voltage-free contacts: with interface card
SIC in the slot COM.
The necessary communication software packages and interface cables are available as options.
Serial interface COM 3
The 9-pole SUB-D connector (pin contacts) contains RS232 compatible signals.
NOTE: The interface COM RS232 is electrically isolated from primary UPS circuits.
Fig. 16: Serial Interface COM3
Interface Slot COM
The interface slot COM can be fitted with various optional interface cards. Interface cards include:
• SNMP-adapter (ManageUPS
NET
) for connecting the device to a network
• isolated contacts card
Refer to the installation guide supplied with the optional interface card.
Communications
With a communications cable and MopUPS
®
Professional installed, MopUPS Professional can exchange
data with the UPS. This power management software polls the UPS for detailed information on the status
of the power environment. If a power emergency occurs, the software initiates an orderly shutdown of the
Pin 2:
RxD (receive RS232 compatible signals)
Pin 3:
TxD (transmit RS232 compatible signals)
Pin 9:
SGN (signal ground for pins)