Appendix A: Features and Specifications
24
Sinergy S II Series Series UPS User Instruction Manual
Physical and Electrical
Specifications
Nominal input voltage:
XAU models (low voltage): 120 V (factory default)
100, 127 V (user selectable)
XHU models (high voltage): 208 V (factory default)
200, 208, 220, 230, 240 (user selectable)
Available output voltage: XAU models (low voltage): 120 V (factory default)
100, 127 V (user selectable)
XHU models (high voltage): 208 V (factory default)
200, 208, 220, 230, 240 (user selectable)
Principle of operation: On-line, double conversion
Surge voltage withstand capability: ANSI/IEEE C62.41 Cat. A & B
Crest factor: 3:1
Recharge time to 90% available capacity: 5 - 8 hours
Total harmonic disortion (linear load): < 4%
Automatic bypass: integrated
Alarms: Mains power, low battery, overload, on bypass
Cooling: Fans
Summary of Contents for S07KXAU