30
ONEAC Sinergy UPS User Manual
Chapter 10 Specifications
Table 7. ONEAC Sinergy UPS (S Series) North America
UPS Model
S700A
S1000XA
S2000XA
S3000XA
Electrical Data
Rating
700 VA
1 kVA
2 kVA
3 kVA
Input
Voltage
120 VAC single-phase
Voltage range A
80 - 138 VAC
Frequency
50/60Hz ± 0.5%
Power factor (lambda)
≥
0.95
Battery
Integrated battery type
Lead-calcium, maintenance-free
Battery voltage (V)
24
36
96
96
Runtimes (min.)
(half load/full load)
17/6
21/7
26/10
17/6
Runtimes (min.),1 battery cabinet
(half load/full load)
NA
85/36
115/49
74/30
Runtimes (min.), 2 battery cabinets
(half load/full load)
NA
140/60
215/92
140/57
Output
Voltage
100/110/120 VAC, single-phase
Voltage tolerance
± 3%
Frequency with mains control
see input frequency
Frequency with internal control
50/60 Hz, ±0. 5%
Distortion factor (linear/non-linear load)
max. 4%/max. 7%
Permissible crest factor
3
Overload capability
130% for 1.5 sec., 110% for 10 sec.
output short-circuit proof