ONEAC Sinergy UPS User Manual
39
Table 14. ONEAC Sinergy UPS (SE Series) North America
UPS Model
SE61XA
(SE41XA*)
SE101XA
(SE81*)
SE203XA
(SE153XA*)
* Models may be upgraded to base kVA of UPS shown.
Electrical Data
Rating
6 kVA
10 kVA
20 kVA
Input
Voltage
208 VAC single-phase
208/120 three-phase
Voltage range
170 V to 276 V
176 to 276 V
177 to 240 V
Frequency
50/60Hz ± 5%
Power factor (lambda)
≥
0.97
≥
0.95
Battery
Integrated battery type
Lead-calcium, maintenance-free
None
Battery voltage (V)
240
Runtimes (min.)
(half load/full load)
25/8
30/12
N/A
Runtimes (min.),1 battery cabinet
(half load/full load)
94/38
100/40
40/15
Output Voltage
Voltage - North American
120, 208, 240 VAC, single-phase
Voltage tolerance
± 3%
Frequency with mains control
see input frequency
Frequency with internal control
50/60 Hz, ± 0.5%
Distortion factor (linear/non-linear load)
max. 4%/max. 7%
max. 5%/ max. 8%
Permissible crest factor
3
Overload capability
130% for 2 sec., 110% for 10 sec.
output short-circuit proof
Common Data
Electrical safety
UL1778
Radio interference level
FCC Part 15 Class A
Interference immunity
IEC 801-2,level 4 / IEC 801-3,level 3
IEC 801-4,level 4 / IEC 801-5,level 2
Efficiency
> 86%
>90%
>85%