40
ONEAC Sinergy UPS User Manual
Cooling
Fan
Common Data (continued)
Noise level mains operation
< 50 dBa
< 55 dBa
<65 dBa
Noise level battery operation
< 55 dBa
<65 dBa
<65 dBa
Operating temperature
+ 50°F to +105°F (+10°C to + 40°C)
recom59°F to +89°F (+15°C to + 32°C)
Storage temperature
+5°F to +104°F (-15°C to +40°C)
Relative humidity
20% to 90%, non-condensing
Altitude
max. 10,000 ft. (3,000m),
above 5,000 ft. (1,500m) max ambient temperature = 95°F (35 °C)
Mechanical Data
UPS
Weight - lbs. (kg)
198 (90)
397 (180)
715 (325)
Dimensions - HxWxD in. (mm)
27.8 x 10.6 x 22.5
(705 x 270 x 570)
38 x 13.4 x 25
(965 x 340 x 670)
46.5 x 16.5 x 31.5
(1180 x 420 x 800)
Battery extension
Type
SBPE61
SBPE101
Weight lbs (kg)
639 (290)
683 (310)
Dimensions - HxWxD in. (mm)
27.8 x 10.6 x 22.5
(705 x 270 x 570)
38 x 15 x 26.4
(965 x 380 x 670)
Signals
Visual
LED-indication at the front side
Audible
Acoustical alarm
Communications
RS232 interface
Alarm co5V...+12V
Signal input +5V...+12V
ethernet
Connections
Mains connections
hardwired
min
8
AWG/6 mm
2
max 6 AWG/16 mm
2
hardwired
min 6 AWG/10 mm
2
max 4 AWG/20 mm
2
hardwired
4 AWG/20 mm
2
Fusing of the mains supply
40
A
70
A
60 A x 5 poles
Table 14. ONEAC Sinergy UPS (SE Series) North America
UPS Model
SE61XA
(SE41XA*)
SE101XA
(SE81*)
SE203XA
(SE153XA*)