ONEAC Sinergy UPS User Manual
4.5 Commissioning of an External Battery Cabinet
The following table shows the designations of the battery cabinets which are available for the UPS devices.
Disconnect the UPS from the mains and the loads from the UPS.
CAUTION: Make sure that the circuit breaker on the external battery cabinet is in the OFF position.
CAUTION: Battery cabinets are not interchangeable. Use ONLY the battery cabinet indicated above.
Connect the battery cabinet types SBP1000, SBP3000 and SBPE61 to the UPS using the supplied cable.
The connection scheme is shown in the figures below. With type SBPE101, make the hard-wired connection
between UPS and the battery cabinet (see figure 22 and 23 on page 20).
Switch the circuit breaker on the battery cabinet to the ON position.
The UPS is now ready for operation.
NOTE: Battery charging times may be longer when using an external battery cabinet.
WARNING:
Fig. 20: Connection of Battery Extensions for devices S1000
Table 3. External Battery Packs
Model
Cabinet
Batteries
S700
NA
NA
S1000
SBP1000
2x (3x7. 2 Ah)
S2000
SBP3000
2x (8x7. 2 Ah)
S3000
SBP3000
2x (8x7. 2 Ah)
SE61 (SE41)
SBPE61
2x (20x7. 2 Ah)
SE101 (SE81)/
SE203 (SE153)
SBPE101
1x (20x38 Ah)
Battery Plug 1
Circuit Breaker
Battery Plug 2