ONEAC Sinergy UPS User Manual
27
Chapter 7 Maintenance
The UPS does not require maintenance by the user. When the battery expires, the UPS or the battery must
be replaced by qualified electrical personnel.
The typical battery’s lifetime is 4 years at an ambient temperature of 25 °C. This may vary greatly depending
upon load conditions, number of outages, and environmental factors.
NOTE: Check periodically (6 to 12 months), to see whether the emergency supply time of the UPS is still
sufficient for its application (See “Ready for Operation Check” on page 21.).
7.1 Storage
For extended storage in moderate climates, the batteries should be charged for 8 hours every three months.
Repeat it every two months in high temperature locations.
1. Connect the UPS to a grounded receptacle or install the types for hard-wire connection according to
chapter 4 “Installation and Commissioning” on page 13 at an appropriate source. Switch on the input
circuit breaker at the rear of the device for hard-wired connection.
2. Pull out the mains plug after 8 hours or switch off the input circuit breaker of the UPS if hard-wired.
Then remove the connections of the UPS in an inverted sequence to what is described in chapter 4
“Installation and Commissioning” on page 13.
3. Note the date of charging on the packing.
NOTE: Make sure all circuit breakers are turned off.
7.2 Cleaning
CAUTION: Press the
switch on the front panel and pull the plug out of the mains receptacle.
NOTE: Type SE61, SE101 and SE203: Press the
switch on the front panel, switch off the input circuit
breaker, isolate the source and secure it against reclosing.
Do not use scouring powder or plastic-dissolving solutions to clean the UPS.
Do not allow liquid to get inside the UPS.
Make sure that the air vents on the UPS are not obstructed.
Clean the outside of the UPS housing by wiping with a dry or a slightly damp cloth.