ONEAC Sinergy UPS User Manual
3
Chapter 2 Display and Operation Elements
The Uninterruptible Power System (UPS) is connected between AC power and the load. It protects the load
against mains disturbances, especially power failures.
Its operation is based on the on-line principle. The connected load is supplied power through the UPS’s
inverter. Power disturbances from the mains are suppressed which increases the loads’ operational security
(PC, network server, multi-user systems etc.)
In the event of a mains failure, maintenance-free batteries provide an uninterrupted supply of energy. In
practice, mains failures are of relatively short duration, dependent on the mains quality. Therefore, the UPS’
energy is in most cases sufficient to ensure continuous operation of the connected systems, until the mains
is reestablished. In the event of a longer lasting mains failure it allows for controlled shutdown of connected
systems.
The UPS indicates by acoustical (buzzer) and optical (LED) alarms that a mains failure has occurred and is
still persistent. Battery runtimes vary depending upon load, number of batteries and environmental
conditions.
The following chart shows the approximate values of the emergency runtime (assuming fully charged
battery at the onset of the mains failure.)
• The actual battery capacity can be read from the LED-”battery” chain (see table below).
The most reliable method for determining actual battery runtime is the application of ONEAC MopUPS
®
software. With this software, the prospective remaining battery capacity is indicated before and during an
AC power failure. Furthermore, shutdown procedures can be automated. Depending on the application
program, operating system and computer hardware, it can be ensured that in the event of a power failure the
application programs are automatically closed, the subscribers logged in at the server are logged out, the
data is stored and the operating systems are shut down. For further information please refer to our
publication about the ONEAC ManageUPS™
NET
SNMP Adapter.
After return of the mains voltage, the UPS automatically initiates a restart. The connected systems are
restarted according to their specifications.
In the event of overload or internal failure, the load is supplied from the mains via an automatic bypass. As
soon as the normal status is reestablished, automatic switchover to inverter operation is performed.
This operation manual contains all relevant information to install and operate the UPS.
Load in %
S700
S1000
S2000
S3000
SE61
SE101
SE203*
OVERLOAD
>105
w/SBPE101
95-105
6 min
7 min
10 min
6 min
9 min
12 min
15 min
LOAD
75-95
7 min
8 min
11 min
7 min
10 min
13 min
20 min
55-75
10 min
11 min
16 min
10 min
13 min
19 min
25 min
35-55
15 min
17 min
24 min
15 min
21 min
25 min
45 min
1-35
28 min
33 min
37 min
28 min
40 min
40 min
90 min
NOTE: *Model SE203 does not contain internal batteries.
Battery Capacity
Battery
1 - 35%
35 - 55%
55 - 75%
75 - 95%
95 - 100%