10hp Direct Drive © O.A.S. 2010
19
Open access cover on the overload, then set the
overload amperage dial to match the FLA amperage
of your motor. The FLA value can be found on your
motor nameplate.
Be sure you have the proper voltage available for your Starter’s Power & Control Circuit (Control
circuit controls Contactor Coil in Starter). Coil voltage is/can be independent from the line voltage that
runs your motor. Customers may desire an alternative Contactor Coil voltage to connect a Starter to a
low voltage control circuit. Most OAS starters are shipped with 240v coils.
Plug the Start / Stop Push-Button Assembly into keyed receptacle. As shown below.)
Run power to the starter and from the starter to your motor. See the manufacturer instructions for
more details.
The Power Circuit connected to the Starter should be fed from a dedicated circuit breaker or discon-
nect with fuses. Don’t connect any branch circuits to the Mag Starter Power Circuit is to be sized
per Article 430.32 of the NEC.
*Use time delay fuses rated for motor circuits.