4.6 ALARMS INTERPRETATION AND LED’s
Alarm Indicators
Symbol
Description
M
When activated, this symbol indicates flow in excess of the set point.
Range: 0-125% of full scale
m
When activated, this symbol indicates flow below the set point.
Range: 0-125% of full scale
!
• Open coil connection
• Signal error
• When activated, indicates empty pipe.
C
Calibration running
S
Transmitter in simulated output mode
W
Pulse output saturated (change pulse rate or
duration)
ALARMS
Status LED
Continuously ON: Initialization of firmware
Flashing LED: (1 second rate): Normal operation
Flashing LED: (<1 second rate): Alarm condition