SECTION 4.0 START-UP AND COMMISSIONING
The display contains two lines of alphanumeric characters. The first line displays the current value. The second line contains
the engineering units and a multiplier which can range from 1 to 1,000,000. The multiplier is the value the number on the
top line must be multiplied by to achieve the correct value.
Three (3) button user interface is provided to operate the display and program the meter.
When operating in the run mode, the SCROLL button advances the display from one page to the next. A total of up to 11
different pages may be available for display depending whether the meter is operating in the single or dual mode.
The RESET button (if enabled) allows totals to be reset to zero. The PROGRAM button is not active when operating in the
run mode.
When power is applied to the BTU meter alphanumeric characters appear on the two lines of the display indicating the
meter is operating. Press and release the SCROLL button on the front panel. Observe the display cycle to the next display
page.
Select the SUPPLY TEMP Page. Note the displayed temperature. Confirm that it is in the expected range. Now select the
RETURN TEMP page. Again note the displayed temperature. Confirm that it is also in the correct range.
Select the FLOW RATE page. Note the displayed flow rate. Confirm that the flow rate value is in the correct range.
Successively pressing the SCROLL button will cycle the display through the run mode pages summarized in the tables on
the next page.
To finalize the installation, follow the procedure outlined in section 4.5 to identify and designate the flow meter location.
4.1 DISPLAY AND USER INTERFACE
4.2 PROCESSOR START-UP