SYSTEM-10 BTU METER
ONICON Incorporated 727.447.6140
Page 9
onicon.com
1.5 ADDITIONAL REQUIRED HARDWARE
1.6 WORKING ENVIRONMENT
The System-10 was designed for installation and use in typical industrial environments that are free of corrosive liquids
and fumes, direct liquid exposure, temperature extremes and vibrations. Do not expose the meter to direct sunlight.
The operating ambient air temperature range is -20° F to 140° F. The electrical power should be relatively clean, free of
high frequency noise, large voltage transients, and protected from power surges and brown outs.
1.7 SERIAL NUMBER
The System-10's serial number is a unique identifier for the product, and is located outside and inside the enclosure. All
components (flow meter, temperature sensors, and main unit) should bear identical serial numbers if ordered together.
Please have this number available when contacting ONICON for assistance.
Flow Meter Model
Line Sizes
Straight Run
Required
Notes
F-1100 Single Turbine Insertion
Flow Meter
1¼” and larger
25
Can be used in 1" copper lines
F-1200 Dual Turbine Insertion
Flow Meter
2½” and larger
15
F-11XX Inline Turbine Flow
Meter
¾” and 1”
25
F-3500 Insertion Electromagnetic
Flow Meter
1¼” and larger
See manual
FSM-3 Series SuperMag
Electromagnetic Flow Meter
6" - 12"
See manual
FT-3000 Series Inline
Electromagnetic Flow Meter
¼” and larger
5
F-2600 Inline Vortex Flow Meter
1/2" - 8"
See manual
F-2700 Insertion Vortex Flow
Meter
3" - 16"
See manual
F-4300 Clamp-on Ultrasonic
Flow Meter
1/2" and larger
See manual
F-4600 Inline Ultrasonic Flow
Meter
1/2"- 21/2"
See manual
ONICON offers a wide variety of flow meters to satisfy most hydronic energy metering applications.
Please refer to ONICON’s flow meter IOM, or contact ONICON for help in selecting the flow meter that will best fit your
requirements.