3.3.5 Temperature Input Wiring Details
1
2
3
4
ONICON FIXED RANGE or LOOP POWERED 4-20mA SCALABLE RANGE
TEMPERATURE INPUTS
TERMINAL BLOCK TB5
1
2
3
4. (+) RETURN TEMP
4
3. SHIELD
2. (-) SUPPLY TEMP
1. (+) SUPPLY TEMP
5
5. (-) RETURN TEMP
(+) Signal
(-) Reference
Return Temperature Sensor
Shield
(+) Signal
(-) Reference
Supply Temperature Sensor
1000 OHMS 4-WIRE PLATINUM RTD TEMPERATURE INPUTS
w/ ATTACHED PIGTAILS CABLE
TERMINAL BLOCK TB6 (SUP)
& TB7 (RET)
4. (B) COMPENSATION LEAD
3. (B) RTD SIGNAL LEAD
2. (A) COMPENSATION LEAD
1. (A) RTD SIGNAL LEAD
Brown*
Yellow*
White*
Green*
1000 OHMS 4-WIRE PLATINUM TEMPERATURE INPUTS
w/ INTEGRAL CONDUIT READY JUNCTION BOX
1
2
3
4
TERMINAL BLOCK TB6 (SUP)
& TB7 (RET)
* Cable color coding to DIN 47100
4. (B) COMPENSATION LEAD
3. (B) RTD SIGNAL LEAD
2. (A) COMPENSATION LEAD
1. (A) RTD SIGNAL LEAD
Refer to Temperature Sensor Connection on page 19 for additional details on the
terminal location.