ONICON Incorporated 727-447-6140
Page 30
www.onicon.com
SYSTEM-20 BTU METER
6.3 DEVICE OBJECT
Property
Default Value
Read-only or
Writable
Comment
Object Identifier
57017
Writable
0-4,194,303
Object Name
System-20-XXXXXX
Read-only
Object Type
Device
Read-only
System Status
Operational
Read-only
Vendor Name
ONICON Inc.
Read-only
Model Name
System-20
Read-only
Firmware Rev.
000.000.000
Read-only
Location
Customer Location
Writable
32 char. Max
Description
Customer Description
Writable
32 char. Max
Protocol Version
1
Read-only
Protocol Revision 10
Read-only
Services
Supported
Read property, Read property multiple,
Write property, Write property multiple,
Read range, Who-has, I have, Who-is, I-am,
Device communications control, Time
synchronization, UTC time synchronization
Read-only
Object Types
Supported
Analog input, Analog value, Binary input,
Device, Multi-state value, Trend log multiple
Read-only
Object List
(Device, 57017), (analog input, 1 – 10),
(analog value, 1 – 24), (binary value, 1 – 10),
(trend log multiple, 1), (multi-state value, 1)
Read-only
Max ADPU Length 480
Read-only
Local Time
Device current time
Read-only
Local Date
Device current date
Read-only
UTC Offset
-300
Writable
Daylight Savings
Status
False
Writable
APDU Time-out
6000
Read-only
# of APDU Retries 3
Writable
Max Master
127
Read-only
Device Address
Binding
N/A
Read-only
Active
Database Revision 1
Read-only