ONICON Incorporated 727-447-6140
Page 32
www.onicon.com
SYSTEM-20 BTU METER
6.6 BINARY VALUE(S)
Property
Default Value
Read-only or Writable
Object Identifier
Binary value 1 to binary value 10
Read-only
Object Name
Various
Read-only
Object Type
Binary-value
Read-only
Present Value
0
Writable
Description
Binary-value,# Name
Read-only
Status Flags
(F,F,F,F)
Read-only
Event State
Normal
Read-only
Reliability
No-fault-detected
Read-only
Out-of-Service
FALSE
Writable
Elapsed Active Time
Various
Read-only
Priority Array
(NULL, NULL, NULL, NULL, NULL, NULL, NULL,
NULL, NULL, NULL, NULL, NULL, NULL, NULL,
NULL, NULL)
Read-only
Relinquish Default
0
Read-only
Binary Value Objects
Object Identifier
Description
Notes
Binary value 1
Mode indication
0 = mode 1, 1 = mode 2
Binary value 2
Location
0 = supply, 1 = return
Binary value 3
Single mode user energy total reset
1 = reset total
Binary value 4
Mode 1 user energy total reset
1 = reset total
Binary value 5
Mode 2 user energy total reset
1 = reset total
Binary value 6
Single mode user volume total reset
1 = reset total
Binary value 7
Mode 1 user volume total reset
1 = reset total
Binary value 8
Mode 2 user volume total reset
1 = reset total
Binary value 9
Aux total 1 reset
1 = reset total
Binary value 10
Aux total 2 reset
1 = reset total
Binary value 11
Aux total 3 reset
1 = reset total
Binary value 12
Flow direction
1 = reverse flow