ONICON Incorporated 727-447-6140
Page 33
www.onicon.com
SYSTEM-20 BTU METER
6.7 MULTI STATE VALUE
Property
Default Value
Read-only or Writable
Object Identifier
Multi state value 1
Read-only
Object Name
Meter Status
Read-only
Object Type
Multi-state-value
Read-only
Present Value
1
Writable
Description
Multi-state-value,# Name
Read-only
Status Flags
(F,F,F,F)
Read-only
Event State
Normal
Read-only
Reliability
No-fault-detected
Read-only
Out-of-Service
FALSE
Writable
Number of States
11
Read-only
State Text
Normal, Low Supply Temperature,
High Supply Temperature, Low Return
Temperature, Delta T< Minimum, High
Energy Rate, Low Signal Quality, Comm
Error, Low Supply Voltage, System Fault
Read-only
Relinquish Default
0
Read-only
Multi-state Object
Object Identifier
Description
Notes
Multi-state value 1
Reports the operating status of the meter
1 = Normal
2 = Low Supply Temperature
3 = High Supply Temperature
4 = Low Return Temperature
5 = High Return Temperature
6 = Delta T < Minimum
7 = High Energy Rate
9 = Comm error
10 = Low Supply Voltage
11= System Fault
Numeric values indicate meter
status.