ONICON Incorporated 727-447-6140
Page 34
www.onicon.com
SYSTEM-20 BTU METER
6.8 TREND LOG MULTIPLE
Property
Default Value
Read-only or Writable
Object Identifier
Trend log multiple 1
Read-only
Object Name
Log Data
Read-only
Object Type
Trend-log-multiple
Read-only
Description
Trend-log-multiple,# Name
Read-only
Status Flags
(F,F,F,F)
Read-only
Event State
Normal
Read-only
Reliability
No-fault-detected
Read-only
Enable
TRUE
Writable
Log Device Property
Read-only
Logging Type
POLLED
Read-only
Log Interval
90000
Writable
Stop When Full
FALSE
Read-only
Buffer Size
480
Read-only
Log Buffer
Read-only
Record Count
0
Writable
Total Record Count
0
Read-only
Trend log Multiple Object
Object Identifier
Description
Notes
Trendlog Multiple 1
Logs the following BACnet objects:
Peak energy rate
Average delta temp
Incremental energy total mode 1
Incremental energy total mode 2
Incremental volume total mode 1
Incremental volume total mode 2
Meter status (multi-state object)
The log buffer holds 120 records and
then rolls over with the first in as first
out.
The logging interval can be set from
30 seconds to 1 hour via BACnet. The
default interval is 15 minutes.