ONICON Incorporated 727-447-6140
Page 37
www.onicon.com
SYSTEM-20 BTU METER
30009
Volume Rate - GPM
Input Register
Floating Point Register (1 of 2)
30010
Volume Rate - GPM
Input Register
Floating Point Register (2 of 2)
30011
Volume Rate - L/s
Input Register
Floating Point Register (1 of 2)
30012
Volume Rate - L/s
Input Register
Floating Point Register (2 of 2)
30013
Volume Rate - ft3/min
Input Register
Floating Point Register (1 of 2)
30014
Volume Rate - ft3/min
Input Register
Floating Point Register (2 of 2)
30015
Volume Rate - m3/hr
Input Register
Floating Point Register (1 of 2)
30016
Volume Rate - m3/hr
Input Register
Floating Point Register (2 of 2)
30017
Flow Temperature - °F
Input Register
Floating Point Register (1 of 2)
Temperature measured by RTD in flow
meter location
30018
Flow Temperature - °F
Input Register
Floating Point Register (2 of 2)
Temperature measured by RTD in flow
meter location
30019
Flow Temperature - °C
Input Register
Floating Point Register (1 of 2)
Temperature measured by RTD in flow
meter location
30020
Flow Temperature - °C
Input Register
Floating Point Register (2 of 2)
Temperature measured by RTD in flow
meter location
30021
Remote Temperature - °F
Input Register
Floating Point Register (1 of 2)
Temperature measured by remote RTD
30022
Remote Temperature - °F
Input Register
Floating Point Register (2 of 2)
Temperature measured by remote RTD
30023
Remote Temperature - °C
Input Register
Floating Point Register (1 of 2)
Temperature measured by remote RTD
30024
Remote Temperature - °C
Input Register
Floating Point Register (2 of 2)
Temperature measured by remote RTD
30025
Delta Temperature - °F
Input Register
Floating Point Register (1 of 2)
30026
Delta Temperature - °F
Input Register
Floating Point Register (2 of 2)
30027
Delta Temperature - °C
Input Register
Floating Point Register (1 of 2)
30028
Delta Temperature - °C
Input Register
Floating Point Register (2 of 2)
30029
Signal Strength (No Units)
Input Register
Floating Point Register (1 of 2)
Range = 1-31; 1 is highest signal
strength; 31 is lowest signal strength
30030
Signal Strength (No Units)
Input Register
Floating Point Register (2 of 2)
Range = 1-31; 1 is highest signal
strength; 31 is lowest signal strength
30031
Signal Quality (No Units)
Input Register
Floating Point Register (1 of 2)
30032
Signal Quality (No Units)
Input Register
Floating Point Register (2 of 2)
30033
Speed Of Sound - ft/sec
Input Register
Floating Point Register (1 of 2)
Measured speed of sound of the fluid in
the pipe
30034
Speed Of Sound - ft/sec
Input Register
Floating Point Register (2 of 2)
Measured speed of sound of the fluid in
the pipe
30035
Speed Of Sound - m/sec
Input Register
Floating Point Register (1 of 2)
Measured speed of sound of the fluid in
the pipe
30036
Speed Of Sound - m/sec
Input Register
Floating Point Register (2 of 2)
Measured speed of sound of the fluid in
the pipe
30037
Energy Total - Single Mode - kBtu
Input Register
Floating Point Register (1 of 2)
30038
Energy Total - Single Mode - kBtu
Input Register
Floating Point Register (2 of 2)
30039
Energy Total - Single Mode - MBtu
Input Register
Floating Point Register (1 of 2)
30040
Energy Total - Single Mode - MBtu
Input Register
Floating Point Register (2 of 2)
30041
Energy Total - Single Mode - TonHr
Input Register
Floating Point Register (1 of 2)
30042
Energy Total - Single Mode - TonHr
Input Register
Floating Point Register (2 of 2)
30043
Energy Total - Single Mode - MJ
Input Register
Floating Point Register (1 of 2)
30044
Energy Total - Single Mode - MJ
Input Register
Floating Point Register (2 of 2)
30045
Energy Total - Single Mode - kWHr
Input Register
Floating Point Register (1 of 2)
30046
Energy Total - Single Mode - kWHr
Input Register
Floating Point Register (2 of 2)
30047
Energy Total - Mode 1 - kBtu
Input Register
Floating Point Register (1 of 2)
30048
Energy Total - Mode 1 - kBtu
Input Register
Floating Point Register (2 of 2)
30049
Energy Total - Mode 1 - MBtu
Input Register
Floating Point Register (1 of 2)